Download ioLogik E2210 Series User`s Manual v8

Transcript
ioLogik E2210 User’s Manual
Eighth Edition, June 2009
www.moxa.com/product
© 2009 Moxa Inc. All rights reserved.
Reproduction without permission is prohibited.
ioLogik E2210 User’s Manual
The software described in this manual is furnished under a license agreement, and may be used only in
accordance with the terms of that agreement.
Copyright Notice
Copyright © 2009 Moxa Inc.
All rights reserved.
Reproduction without permission is prohibited.
Trademarks
MOXA is a registered trademark of Moxa Inc.
All other trademarks or registered marks in this manual belong to their respective manufacturers.
Disclaimer
Information in this document is subject to change without notice, and does not represent a commitment on the
part of Moxa.
Moxa provides this document “as is,” without warranty of any kind, either expressed or implied, including, but
not limited to, its particular purpose. Moxa reserves the right to make improvements, and/or changes to this
manual, or to the products, and/or the programs described in this manual, at any time.
Information provided in this manual is intended to be accurate, and reliable. However, Moxa assumes no
responsibility for its use, or for any infringements on the rights of third parties that may result from its use.
This manual might include unintentional technical or typographical errors. Changes are made periodically to the
information herein to correct such errors, and these changes are incorporated into new editions of the manual.
Technical Support Contact Information
www.moxa.com/support
Moxa Americas:
Toll-free: 1-888-669-2872
Tel: +1-714-528-6777
Fax: +1-714-528-6778
Moxa China (Shanghai office):
Toll-free: 800-820-5036
Tel: +86-21-5258-9955
Fax: +86-10-6872-3958
Moxa Europe:
Tel: +49-89-3 70 03 99-0
Fax: +49-89-3 70 03 99-99
Moxa Asia-Pacific:
Tel: +886-2-8919-1230
Fax: +886-2-8919-1231
Table of Contents
Chapter 1.
Introduction ...............................................................................................1-1
Overview .............................................................................................................................. 1-2
Traditional Remote I/O................................................................................................. 1-2
Active Ethernet I/O....................................................................................................... 1-2
Click&Go ..................................................................................................................... 1-3
Optional Liquid Crystal Display Module (LCM) ......................................................... 1-3
Product Features ................................................................................................................... 1-3
Packing List.......................................................................................................................... 1-3
Product Specifications .......................................................................................................... 1-4
Physical Dimensions ............................................................................................................ 1-5
Without LCD Module................................................................................................... 1-5
With LCD Module........................................................................................................ 1-6
Hardware Reference ............................................................................................................. 1-7
Panel Guide .................................................................................................................. 1-7
LED Indicators ............................................................................................................. 1-8
Chapter 2.
Initial Setup ................................................................................................2-1
Hardware Installation ........................................................................................................... 2-2
Connecting the Power................................................................................................... 2-2
Grounding the ioLogik E2210 ...................................................................................... 2-2
Connecting to the Network........................................................................................... 2-2
Setting the RS-485 Baudrate ........................................................................................ 2-2
Adding More I/O Channels .......................................................................................... 2-3
Software Installation............................................................................................................. 2-3
Chapter 3.
Using ioAdmin ...........................................................................................3-1
Introduction to ioAdmin ....................................................................................................... 3-2
Features of ioAdmin ............................................................................................................. 3-2
ioAdmin Main Screen........................................................................................................... 3-4
Main Screen Overview ................................................................................................. 3-4
Wiring Guide ................................................................................................................ 3-5
Main Items............................................................................................................................ 3-6
File................................................................................................................................ 3-6
System .......................................................................................................................... 3-6
Sort ............................................................................................................................... 3-7
Help .............................................................................................................................. 3-7
Quick Links .................................................................................................................. 3-7
Main Window ....................................................................................................................... 3-8
I/O Configuration Tab (General) .................................................................................. 3-8
Server Info Tab............................................................................................................. 3-8
Server Settings Tab (General) ...................................................................................... 3-9
Message Monitor Tab ................................................................................................... 3-9
ioAdmin Administrator Functions ...................................................................................... 3-10
I/O Configuration Tab (Administrator) ...................................................................... 3-10
Server Settings Tab (Administrator)........................................................................... 3-14
Network Tab ............................................................................................................... 3-16
Firmware Update Tab ................................................................................................. 3-17
Watchdog Tab............................................................................................................. 3-17
Click&Go Logic Tab .................................................................................................. 3-18
Active Tags Tab.......................................................................................................... 3-19
SNMP Settings Tab .................................................................................................... 3-20
Server Context Menu.......................................................................................................... 3-20
Using TFTP to Import/Export Configuration ..................................................................... 3-22
Using ioEventLog............................................................................................................... 3-23
Installing ioEventLog ................................................................................................. 3-23
Basic Functions........................................................................................................... 3-23
Configuration.............................................................................................................. 3-24
Checking Connected Devices ..................................................................................... 3-25
Opening Log Files ...................................................................................................... 3-25
Clearing the Log ......................................................................................................... 3-25
Chapter 4.
Using the Web Console ............................................................................4-1
Introduction to the Web Console .......................................................................................... 4-2
Basic Settings ....................................................................................................................... 4-3
Network Settings .................................................................................................................. 4-3
General Settings............................................................................................................ 4-3
Ethernet Configuration ................................................................................................. 4-4
RS-485 Settings ............................................................................................................ 4-4
I/O Settings........................................................................................................................... 4-5
DI Channels .................................................................................................................. 4-5
DO Channels ................................................................................................................ 4-6
System Management ............................................................................................................ 4-7
Accessible IP Settings................................................................................................... 4-7
SNMP Agent ................................................................................................................ 4-8
Network Connection..................................................................................................... 4-8
Firmware Update .......................................................................................................... 4-9
Import System Config .................................................................................................. 4-9
Export System Config .................................................................................................. 4-9
LCM ................................................................................................................................... 4-10
Change Password................................................................................................................ 4-10
Load Factory Default.......................................................................................................... 4-10
Save/Restart........................................................................................................................ 4-10
Chapter 5.
Active OPC Server Lite .............................................................................5-1
OLE for Process Control ...................................................................................................... 5-2
Introduction to Active OPC Server Lite ............................................................................... 5-2
Active OPC Server Lite – From Pull to Push ....................................................................... 5-3
Features of Active OPC Server Lite ..................................................................................... 5-4
Active OPC Server Lite Specifications ................................................................................ 5-5
Installation of Active OPC Server Lite......................................................................... 5-5
Installation of OPC Core Components ......................................................................... 5-5
Active OPC Server Lite........................................................................................................ 5-6
Main Screen Overview ................................................................................................. 5-6
Menu Items........................................................................................................................... 5-7
File................................................................................................................................ 5-7
System .......................................................................................................................... 5-7
Sort ............................................................................................................................... 5-8
Quick Links .................................................................................................................. 5-8
Tag Generation ..................................................................................................................... 5-8
Push Tag Configuration from ioAdmin ........................................................................ 5-8
Advanced Settings ...................................................................................................... 5-10
Heartbeat Interval ....................................................................................................... 5-11
Read/Write Privilege .................................................................................................. 5-11
OPC Test Client.......................................................................................................... 5-11
Appendix A.
Liquid Crystal Display Module (LCM) ..................................................... A-1
Appendix B.
Modbus/TCP Address Mappings ............................................................ B-1
0xxxx Read/Write Coils (Functions 1, 5, 15) .......................................................................B-1
1xxxx Read Only Coils (Function 2)....................................................................................B-4
3xxxx Read Only Registers (Function 4) .............................................................................B-4
4xxxx Read/Write Registers (Functions 3, 6, 16).................................................................B-5
Appendix C.
Used Network Port Numbers................................................................... C-1
Appendix D.
SNMP MIB II .............................................................................................. D-1
Appendix E.
CGI Commands ........................................................................................ E-1
Appendix F.
Factory Defaults ........................................................................................F-1
Appendix G.
Pinouts and Cable Wiring........................................................................ G-1
Ethernet Port Pinouts ........................................................................................................... G-1
Serial Port Pinouts ............................................................................................................... G-1
Digital Input Wiring ............................................................................................................ G-1
Structure ...................................................................................................................... G-1
Dry Contact ................................................................................................................. G-2
Wet Contact ................................................................................................................. G-2
Example....................................................................................................................... G-2
Digital Output...................................................................................................................... G-3
Structure ...................................................................................................................... G-3
Output Channel............................................................................................................ G-3
Pin Assignment of Terminal Blocks .................................................................................... G-4
Appendix H.
Federal Communication Commission Interference Statement ............ H-1
Appendix I.
European Community (CE)........................................................................I-1
1
Chapter 1.
Introduction
The ioLogik E2210 is a stand-alone Active Ethernet I/O server that can connect sensors and on/off
switches for automation applications over Ethernet and IP-based networks.
The following topics are covered in this chapter:
‰
‰
‰
‰
‰
‰
Overview
¾ Traditional Remote I/O
¾ Active Ethernet I/O
¾ Click&Go
¾ Optional Liquid Crystal Display Module (LCM)
Product Features
Packing List
Product Specifications
Physical Dimensions
¾ Without LCD Module
¾ With LCD Module
Hardware Reference
¾ Panel Guide
¾ LED Indicators
ioLogik E2210 User’s Manual
Introduction
Overview
(shown with and without optional LCM)
The ioLogik E2210 is part of the E2000 line of ioLogik Active Ethernet I/O servers, which are
designed for intelligent, pro-active status reporting of attached sensors, transmitters, transducers,
and valves over a network. It includes 2 MB of Flash ROM, 8 MB of SDRAM, and supports an
optional hot-pluggable Liquid Crystal Display Module (LCM) to view and configure device
settings.
Traditional Remote I/O
Ethernet remote I/O solutions have been on the market for a long time. Traditional solutions are
“passive,” in the sense that I/O servers wait passively to be polled by a host computer. The response
time in this type of setup, however, tends to be on the order of seconds. The “passive” remote I/O
structure is simply inadequate for data acquisition and control systems that require an efficient,
real-time I/O solution with a response time on the order of hundredths of seconds.
Active Ethernet I/O
Moxa’s Active Ethernet I/O line was developed specifically to address the limitations of the
traditional passive approach. Rather than having the host computer poll the I/O device server over
the network for the status of each I/O device, the Active Ethernet I/O server intelligently sends the
host computer status information only under specified conditions. This is a report by exception
approach, which greatly reduces the load on CPU and network resources. Network packets are far
fewer in number and far smaller in size, since I/O information is only sent when necessary, and only
information from the specified I/O device is sent. Based on field tests of an ioLogik E2000 series
server used in an RFID system, 50 ms is the typical response time over a 100 Mbps Ethernet network.
Moxa’s active I/O messaging system uses TCP or UDP for I/O messaging and supports sending
messages to up to ten host computers simultaneously.
In addition to providing intelligent status reporting, Active Ethernet I/O servers are backwards
compatible, with all of the functions and capabilities of traditional passive remote I/O servers.
1-2
ioLogik E2210 User’s Manual
Introduction
Click&Go
Moxa developed the Click&Go logic control interface for easy configuration and deployment of
Active Ethernet I/O. Click&Go’s intuitive, graphical interface lets administrators use simple
IF/THEN statements as rules to determine how the Active Ethernet I/O server responds to different
I/O conditions. For example, the Active Ethernet I/O server could be programmed to turn on an
attached switch as well as send an e-mail or SNMP trap when an attached event counter reaches a
certain value. Click&Go makes it easy to define a set of these rules, which will become the basis for
your Active Ethernet I/O system.
Optional Liquid Crystal Display Module (LCM)
As a Moxa Easy View product, the ioLogik E2210 supports an optional hot-pluggable Liquid
Crystal Display Module (LCM) for field management and configuration. The LCM can display
network and I/O settings such as digital input mode and value. The ioLogik E2210’s IP address and
netmask may also be configured using the LCM, and one LCM can be used to maintain and
configure all your Easy View devices.
Product Features
z
Click&Go logic builder for easy configuration of your Active Ethernet I/O system
z
High-speed active I/O messaging
z
12-channels of 24 VDC digital input (DI) with DI/Event Counter mode and software selectable
filtering time
z
8-channels of 24 VDC digital output (DO) with Pulse Output mode and software selectable
pulse width
z
10/100 Mbps Ethernet with Modbus/TCP protocol connecting up 10 hosts
z
Bundled Windows utility and quick programming library for VB, VC++, BCB
z
Supports RS-485 modules for expandable I/O
z
Supports SCADA software such as Wonderware InTouch and GE Intellution iFix32
z
SNMP for system management and I/O status
z
Remote management over the network including firmware updates
z
Supports use of TFTP server to import configuration
z
Configurable DO power-on and safe status settings
z
Optional hot-pluggable LCM for status display and configuration
Packing List
The ioLogik E2210 is shipped with the following items:
Standard Accessories
z
ioLogik E2210 Active Ethernet I/O Server
z
Document and Software CD
Optional Accessories
z
LDP1602 ioLogik Liquid Crystal Display Module (LCM)
NOTE: Notify your sales representative if any of the above items are missing or damaged.
1-3
ioLogik E2210 User’s Manual
Introduction
Product Specifications
LAN
Ethernet
Protection
Protocols
Serial
Interface
Serial Line Protection
10/100 Mbps, RJ45
1.5 KV magnetic isolation
Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, SNMP(MIB for I/O
and Network), HTTP
RS-485 (2-wire): Data+, Data-, GND
15 KV ESD for all signals
Serial Communication parameters
None
Parity
8
Data Bits
1
Stop Bits
None
Flow Control
1200 to 115200 bps
Speed
Modbus/RTU
Protocol
Yes
Built-in RTC
Digital Input
12, source type
Inputs
DI or Event Counter (input frequency: 900 Hz)
I/O Mode
Logic 0: short to GND, Logic 1: open
Dry Contact
Logic 0: 0 to 3 VDC,
Wet Contact
Logic 1: 10 to 30 VDC (DI COM to DI)
12 points / 1 COM
Common Type
2000 VRMS / 3000 VDC
Isolation
Digital Output
8, sink type
Outputs
24 VDC nominal
On-state Voltage
Max. 200 mA per channel
Output Current Rating:
2000 VRMS / 3000 VDC
Optical Isolation
Over temperature shutdown: 170°C
Protection
Over current limit: 750 mA/channel (typical)
Power Requirement
24 VDC nominal, 12 to 48 VDC
Power Input
282 mA @ 24 VDC (typical)
Power Consumption
24 VDC nominal, up to 48 VDC
Field Power
Mechanical Specifications
I/O cable max. 14 AWG
Wiring
Environmental
-10 to 60ºC (14 to 140ºF), 5 to 95%RH
Operating Temperature
-40 to 85ºC (-4 to 185ºF), 5 to 95%RH
Storage Temperature
IEC60068-2-27
Shock
IEC60068-2-32
Freefall
IEC60068-2-6
Vibration
Agency Approvals
FCC Part 15, CISPR (EN55022) Class A
EMC
CE: IEC 61000-4-2 (ESD), Level 2/3
IEC 61000-4-3 (RS), Level 2
IEC 61000-4-4 (EFT), Level 2
1-4
ioLogik E2210 User’s Manual
Introduction
IEC 61000-4-5 (Surge), Level 3
IEC 61000-4-6 (CS), Level 2
IEC 61000-4-8 (PM), Level 1
IEC 61000-4-11 (DIP)
IEC 61000-6-2
IEC 61000-6-4 (EMC)
UL 508, EN61000-6-2, EN61000-6-4
2 years
Safety
Warranty
Physical Dimensions
Without LCD Module
5.95
45.39
24.44
9.5
79
39.5
9.51
10.7
10.98
93.02
115
121.8
Unit=mm
1-5
46.51
6
ioLogik E2210 User’s Manual
Introduction
With LCD Module
5.95
45.63
24.44
9.5
79
39.5
9.51
10.7
6
46.51
93.02
115
121.8
10.98
44.5
3.4
79
3.39
35.1
6.89
Unit=mm
57.5
Unit=mm
1-6
ioLogik E2210 User’s Manual
Introduction
Hardware Reference
Panel Guide
(TB1/TB2)
(TB3)
NOTE – The reset button restarts the server and resets all settings to factory defaults. Use a pointed
object such as a straightened paper clip to hold the reset button down for 5 sec. The RDY LED will
turn red as you are holding the reset button down. The factory defaults will be loaded once the RDY
LED turns green again. You may then release the reset button.
1-7
ioLogik E2210 User’s Manual
Introduction
LED Indicators
Ethernet
Ethernet
Orange
Green
(flashing)
Connected to a 10 Mbps Ethernet connection.
Connected to a 100 Mbps Ethernet connection.
Transmitting or receiving data
System
PWR
RDY
Serial
I/O
DI × 12 pins
DO × 8 pins
DO PWR
Red
Off
red
green (steady)
green (flashing)
green & red (flashing)
off
(flashing)
green
off
red
off
Power is on
Power is off
System error
Unit is functioning normally
Click&Go ruleset is active
Unit is in Safe Status
Power is off or there is a power problem.
Serial port is receiving/transmitting data
ON status
OFF status
ON status
No power connected
1-8
2
Chapter 2.
This chapter describes how to install the ioLogik E2210.
The following topics are covered:
‰
‰
Hardware Installation
¾ Connecting the Power
¾ Grounding the ioLogik E2210
¾ Connecting to the Network
¾ Setting the RS-485 Baudrate
¾ Adding More I/O Channels
Software Installation
Initial Setup
ioLogik E2210 User’s Manual
Initial Setup
Hardware Installation
Connecting the Power
Connect the 12 to 48 VDC power line to the ioLogik E2210’s terminal block (TB1). If power is
properly supplied, the Power LED will glow a solid red color until the system is ready.
ATTENTION
Disconnect the power before installing and wiring
Disconnect the power cord before installing and/or wiring your ioLogik E2210.
Do not exceed the maximum current for the wiring
Determine the maximum possible current for each power wire and common wire. Observe all
electrical codes dictating the maximum current allowable for each wire size.
If the current exceeds the maximum rating, the wiring could overheat, causing serious damage to
your equipment.
Grounding the ioLogik E2210
The ioLogik E2210 is equipped with two grounding points, one on the wall mount hole and the other
on the DIN-rail mount.
Note that both grounding points are actually connected to the same conducting pathway.
Connecting to the Network
1.
Connect the ioLogik E2210 to the host PC with an Ethernet cable. For initial setup of the
ioLogik E2210, it is recommended that the ioLogik E2210 be configured using a direct
connection to a host computer rather than remotely over the network.
2.
Configure the host PC’s IP address to 192.168.127.xxx. (xxx: from 001 to 253). In Windows,
you will need to do this through the Control Panel.
ioLogik E2210 Default IP Address
192.168.127.254
3.
Default Netmask
255.255.255.0
Default Gateway
None
Use ioAdmin or the web console to detect the ioLogik E2210. Once the ioLogik E2210 has
been detected, modify the settings as needed for your network environment, then restart the
server.
Setting the RS-485 Baudrate
The RS-485 port on the ioLogik E2210 is reserved to chain another RS-485 I/O server. The RS-485
port can run Modbus/RTU or I/O command sets. The baudrate is set by a physical dial on the back of
the ioLogik E2210. The default settings are baudrate = 115200, parity check = N, data bits = 8, and
stop bit = 1.
Baudrate for RS-485
(parameters are N, 8, 1)
Dial setting and corresponding baudrate:
0:115200 1:57600
2:38400
3:19200
4:9600
5:4800
6:2400
7:1200
Remember to restart the ioLogik E2210 after making any changes to the RS-485 baudrate.\
2-2
ioLogik E2210 User’s Manual
Initial Setup
Adding More I/O Channels
A cost-effective way to add more I/O channels to your ioLogik E2000 I/O server is to attach the
appropriate ioLogik R2000 I/O server. The two servers can be snapped together using the RS-485
system bus connector, as shown in the following figure. For the ioLogik E2210, additional digital
I/O channels are added using the ioLogik R2110. For additional details, please refer to the ioLogik
R2110 user’s manual.
Software Installation
ioAdmin is a Windows utility provided for the configuration and management of the ioLogik E2210
and attached I/O devices. It may be used from anywhere on the network to monitor and configure the
ioLogik E2210. You may also configure some of the settings through the web console or optional
LCM.
1.
Installation from CD: Insert the Document and Software CD into the host computer. In the
root directory of the CD, locate and run SETUP.EXE. The installation program will guide you
through the installation process and install the ioAdmin utility. You can also install the MXIO
DLL library or ioEventLog separately.
2.
Open ioAdmin: After installation is finished, run ioAdmin from Start Æ Program Files Æ
MOXA ÆIO Server Æ Utility Æ ioAdmin.
3.
Search the network for the server: On the menu bar, select System ÆAuto Scan Active
Ethernet I/O Server. A dialog window will pop up. Click Start Search to begin searching for
the ioLogik E2210.
2-3
ioLogik E2210 User’s Manual
Initial Setup
If ioAdmin is unable to find the ioLogik E2210, there may be a problem with your network settings.
If multiple ioLogik E2000 units are installed on the same network, remember that each unit has
the same default IP address. You will need to assign a different IP address to each unit to avoid
IP conflicts. ioAdmin automatically detects IP conflicts and gives you a chance to modify each
unit’s IP address in the "IP Address" columns. Click the "Set" button to reboot the
corresponding unit with its new IP address. Click the "Re-Search" button to refresh the list of
units found by ioAdmin.
4.
Monitoring I/O status: Once the ioLogik E2210 is found by ioAdmin, you may view the
status of all I/O devices on ioAdmin’s main screen.
You may now use ioAdmin to set up or configure your ioLogik E2210.
2-4
3
Chapter 3.
Using ioAdmin
This chapter goes over the functions available in ioAdmin, the ioLogik E2210’s main configuration
and management utility.
The following topics are covered:
‰
‰
‰
‰
‰
‰
‰
‰
‰
Introduction to ioAdmin
Features of ioAdmin
ioAdmin Main Screen
¾ Main Screen Overview
¾ Wiring Guide
Main Items
Main Window
¾ I/O Configuration Tab (General)
¾ Server Info Tab
¾ Server Settings Tab (General)
¾ Message Monitor Tab
ioAdmin Administrator Functions
¾ I/O Configuration Tab (Administrator)
¾ Server Settings Tab (Administrator)
¾ Network Tab
¾ Firmware Update Tab
¾ Watchdog Tab
¾ Click&Go Logic Tab
¾ Active Tags Tab
¾ SNMP Settings Tab
Server Context Menu
Using TFTP to Import/Export Configuration
Using ioEventLog
¾ Installing ioEventLog
¾ Basic Functions
¾ Configuration
¾ Checking Connected Devices
¾ Opening Log Files
¾ Clearing the Log
ioLogik E2210 User’s Manual
Using ioAdmin
Introduction to ioAdmin
The ioLogik I/O server may be managed and configured over the Ethernet by ioAdmin, a Windows
utility provided with your ioLogik E2210. ioAdmin’s graphical user interface gives you easy access
to all status information and settings.
The ioLogik E2210 also supports configuration by web console and by optional LCM, but full
configuration and management is only available through ioAdmin.
A new feature in ioAdmin automatically detects IP conflicts between ioLogik E2000 units. If
ioAdmin detects an IP conflict, a window will appear that allows you to resolve the IP conflict
immediately and restart each unit.
ioAdmin also includes Click&Go logic control for the configuration of your Active Ethernet I/O
system.
ioAdmin consists of following software:
y
ioAdmin with Click&Go Logic
y
ioLogik 2000 Wiring Guide
y
ioLogik 4000 Wiring Guide
Features of ioAdmin
Remote Management
Over the Ethernet network,
ioAdmin allows users to
y find and configure
multiple ioLogik
servers.
y monitor and configure
attached I/O devices.
y test I/O devices.
y reset the server.
On-line Wiring Guide
An on-line wiring guide
can be opened from within
ioAdmin for your
convenience. The easily
accessible wiring guide
can save administrators
much time while planning
or troubleshooting.
3-2
ioLogik E2210 User’s Manual
Using ioAdmin
Configuration File
ioAdmin allows the entire
configuration of the
ioLogik E2210 to be saved
as a file. The file is
viewable as text and can
serve three purposes:
z
z
z
as a record or backup
of configuration
as a template for the
configuration of other
servers
as a quick reference
guide for you to
configure Modbus
drivers in a SCADA
system
The file includes the
following information:
z
file title, date, and time
model information
z Modbus address
Server Management List
ioAdmin can import and
export a list of ioLogik
servers that are being
managed. This file can
make it easier to manage
all devices on the network,
and includes the following
information:
z
z
z
z
z
server name
module type
IP address
unit ID
3-3
ioLogik E2210 User’s Manual
Using ioAdmin
ioAdmin Main Screen
Main Screen Overview
This is ioAdmin’s main screen. The main window defaults to the I/O Configuration tab, which
displays a figure of the ioLogik E2210 and the status of every I/O channel below it. The other tabs in
the main window take you to server and network settings, and further functions are available when
you log on as an administrator. Note that configuration options are not available until you log on as
an administrator.
1
3
2
4
5
6
7
ioAdmin Main Screen
1.
Title
2.
Menu bar
3.
Quick link
4.
Navigation panel
5.
Main window
6.
Sync. rate status
7.
Status bar
3-4
ioLogik E2210 User’s Manual
Using ioAdmin
Wiring Guide
ioAdmin provides a wiring guide to the ioLogik E2210. You may access the wiring guide by
right-clicking the figure of the ioLogik E2210 in the I/O Configuration tab. Select “Wiring Guide” in
the submenu to open a help file showing the wiring information and electrical characteristics of the
ioLogik E2210.
You may also access the On-line Wiring Guide through the Help menu on the menu bar.
3-5
ioLogik E2210 User’s Manual
Using ioAdmin
Main Items
File
From the File menu, you can export the list of I/O servers that are currently displayed in the
navigation panel. You also can import a list of I/O servers into ioAdmin.
When importing a server list, you will be prompted to select which servers on the list need to be
imported.
The file will have a .SLT extension and can be opened as a text file. The server list will provide the
following information for each server:
z
z
z
z
server name
module type
IP address
unit ID
System
Several operations are possible from the System menu.
Auto Scan Active Ethernet I/O Server will search for ioLogik servers on the network. When
connecting for the first time or recovering from a network disconnection, you can use this
command to find I/O servers that are on the network.
Network Interface allows you to select a network to use, if the PC has multiple network adapters
installed.
I/O Status Refresh Rate is used to adjust how often the I/O server is polled for device status. The
current rate is displayed on the status bar at the bottom of the window. Note that higher sync rates
result in higher loads on the network.
TCP Socket Timeout Interval allows you to select the preferred timeout value for TCP socket
communication.
3-6
ioLogik E2210 User’s Manual
Using ioAdmin
COM Port Setting is used to set the parameters for Modbus communciation, such as baudrate,
data bits, and timeout interval. For most applications, this will involve connecting to ioLogik
R-Series devices.
Active Message Listen Port specifies the port number to use for Active Ethernet I/O messages. If
your network uses a firewall, you can coordinate this setting with your firewall settings to ensure
that active messages get through.
Reset NA4010 Network Adapter IP is used to re-assign an IP address to the NA-4010 network
adapter, for ioLogik 4000 systems.
Sort
The Sort menu allows the server list in the navigation panel to be sorted by connection, type, and
location.
Help
In the Help menu, you can view wiring guides and information about ioAdmin.
Quick Links
Quick links are provided to search for I/O servers on the network and sort the server list.
Search network for I/O servers
Sort by connection
Sort by I/O server type
Sort by location
3-7
ioLogik E2210 User’s Manual
Using ioAdmin
Main Window
I/O Configuration Tab (General)
The I/O Configuration tab shows the status of every I/O channel. This is the default tab when you
first open ioAdmin.
Server Info Tab
Server information, such as firmware revision, is displayed in the Server Info tab.
3-8
ioLogik E2210 User’s Manual
Using ioAdmin
Server Settings Tab (General)
The Server Settings tab is where you log in as an administrator. This is required in order to gain
access to the ioLogik E2210 configuration options. If no administrator password has been set up,
simply click on Login and leave the Password for entry field blank. Additional detail is provided
later in this chapter.
Message Monitor Tab
The Message Monitor tab will display any TCP/UDP I/O messages received from the ioLogik
E2210. When you install the ioLogik E2210 for the first time, the active I/O messaging ruleset will
not have been defined yet, so there will be no messages in the Message Monitor Tab. Please refer to
Chapter 5 for information on how to program the ioLogik E2210’s active I/O messaging system.
Once the active I/O messaging system has been configured and activated, TCP/UDP messages sent
from the ioLogik E2210 will be viewable in the Message Monitor tab.
Messages can be displayed in ASCII or in HEX. To display messages in HEX, make sure that
“Toggle HEX” is checked.
3-9
ioLogik E2210 User’s Manual
Using ioAdmin
ioAdmin Administrator Functions
For full access to all configuration options, log in as an administrator in the Server Settings tab. This
is required whenever you start up ioAdmin or boot up/restart the ioLogik E2210. When you install
the ioLogik E2210 for the first time, the password will be blank and you may simply click on Login.
Additional functions will available after logging in, including the following new tabs:
When making configuration changes, you will need to click on Update or on Apply to save the
changes. Some changes will require a restart of the ioLogik E2210 in order to take effect, and you
will be given the option to restart the computer if necessary.
ATTENTION
You must log in to access any administrator function, including Network, Communication
Watchdog Timer, and Firmware Update tabs. If you forget the password, you may hold down the
ioLogik’s reset button to clear the password and load factory defaults. This will result in the loss
of all configuration settings and your Click&Go Logic active I/O messaging program!
I/O Configuration Tab (Administrator)
When logged on as an administrator, you may double click on a channel in the I/O Configuration
tab to configure that channel’s settings. A window will open with configuration options for that
channel. Settings made in this window can be copied to all I/O channels using the “Apply to all
channels” option. Options for Power On Settings and Safe Status Settings are also available.
Configuring Digital Input Channels
Alias Name
Click the Alias Name tab to customize the channel name. You may use names with up to 16
characters. If you have already set the Alias Name on the I/O Configuration page, the channel
name will appear in Click&Go, Active message, and Web.
3-10
ioLogik E2210 User’s Manual
Using ioAdmin
The E2210 is equipped with 12 DI (digital input) channels that can be separately set to “DI” or
“Event Counter Mode.” In DI mode, the specifications are as follows:
Type
Dry contact
Wet contact
Logic 0
close to GND
0 to 3 V
Logic 1
open
10 to 30 V
In Event Counter mode, the ioLogik E2210’s DI channel accepts limit or proximity switches and
counts events according to the ON/OFF status. You may select from two modes, “Lo to Hi” or “Hi to
Lo.” When “Lo to Hi” is selected, the counter value increases while the switch is pushed. When “Hi
to Lo” is selected, the counter value increases when the switch is push and released.
To control switch bounces, the ioLogik E2210 provides software filtering. It is configurable in
multiples of 0.5 ms. For example, a setting of 2 would mean a 1 ms filter (2 × 0.5 ms). The maximum
value allowed by the software filter is 65535.
NOTE: “1” is the minimum filter value.
Configuring Digital Output Channels
3-11
ioLogik E2210 User’s Manual
Using ioAdmin
The ioLogik E2210 is equipped with 8 DO (digital output or sink) channels that can be set
individually to “DO” or “Pulse Output” mode.
In DO mode, the specification is as follows.
Type
DO mode
Logic 0
Open
Logic 1
Short
In Pulse Output mode, the selected digital output channel will generate a square wave as specified in
the pulse mode parameters. The low and high level widths are entered in multiples of 0.5ms, with a
maximum setting of 65,535 (32,767 ms).To set the low level width for 500 ms, you would enter
1000 (because 1000 × 0.5 ms = 500 ms). If the low width value is 5000 and the high width value is
5000, the pulse output would be a square wave with a 5-second pulse cycle. If continuous pulse
output is desired, enter “0” for the number of pulses, otherwise enter the desired number of pulses
between 1 and 4,294,967,295.
3-12
ioLogik E2210 User’s Manual
Using ioAdmin
Power on Settings
Use this field to set the initial behavior of the DI/O channel when the ioLogik E2210 is powered on.
For DI channels in Event Counter mode, you may configure whether or not counting begins at power
up. For DO channels in DO mode, you may configure whether or not the DO is set to OFF or ON at
power up. For DO channels in Output Pulse mode, you may configure whether or not the pulse
output commences at power up.
Safe Status Settings
Use this field to specify how the DI/O channel behaves when the network connection is lost. When
the network connection is lost for the amount of time specified in the Host Connection Watchdog,
the ioLogik E2210 enters Safe Status, and each DI/O channel’s Safe Status settings will go into
effect. Note that the Host Connection Watchdog is disabled by default. If the Host Connection
Watchdog is disabled, the ioLogik E2210 will never enter Safe Status and the Safe Status settings
will have no effect.
For DI channels in Event Counter mode, you can configure whether or not counting starts or
continues when Safe Status has been activated. For DO channels in DO mode, you can configure
whether or not the DO is set to OFF or ON at Safe Status. For DO channels in Output Pulse mode,
you can configure whether or not the output pulse commences or continues at Safe Status.
Test I/O
You may test the DI/O channel by using ioAdmin.
.
DI-DI: show the channel’s status
DI-Counter: start or stop the counter
DO-DO: set the DO to “ON” or “OFF”
DO-Pulse: activate or stop pulse generation.
3-13
ioLogik E2210 User’s Manual
Using ioAdmin
Server Settings Tab (Administrator)
You may set the password, server name, location, date, time, time zone, and time server in the
Server Settings tab. ioAdmin supports long server names and a location description up to 58
characters.
You may set up the Daylight Saving schedule by clicking the “Daylight Saving” button. You may
choose EU type, US type, or User defined type. User defined type allows you to define the days
and offset hours.
3-14
ioLogik E2210 User’s Manual
Using ioAdmin
If you will be using ioEventLog to receive server status reports, such as for warm or cold starts,
you need to specify the IP address and port number for the PC that will be running ioEventLog in
the “System Log” field. The default port number is 4040. For additional information, please refer
to the ioEventLog section later in this chapter.
3-15
ioLogik E2210 User’s Manual
Using ioAdmin
Network Tab
The Network tab is where you configure IP settings, Modbus/TCP Alive Check Timeout settings,
DNS settings, Serial settings, and Web Access settings for the ioLogik E2210.
IP Settings: You can set up a static or dynamic IP address for the ioLogik E2210, as well as the
subnet mask and gateway address. The Accessible IP screen can be used to control network access
to the ioLogik E2210 and attached sensors. Network requests that originate from sources that are not
listed in the accessible IP list will be unable to use Modbus/TCP or ioAdmin to access the ioLogik
E2210.
Modbus/TCP Alive Check Timeout Settings: The Modbus/TCP Alive Check Timeout is designed
to avoid TCP connection failure. When the host is down, the ioLogik E2210 will continue to wait for
a response from the host. This will cause the TCP port to be indefinitely occupied by the host. When
the Modbus/TCP idle connection timeout interval is enabled, the ioLogik E2210 will close the TCP
connection automatically if there is no TCP activity for the specified time. Please note that
Modbus/TCP connections will be blocked when setting up Accessible IP.
DNS Settings: Use this field to specify up the IP addresses of up to 2 DNS servers. These two DNS
servers may be used to automatically find available e-mail addresses when configuring for Active
Ethernet I/O e-mail messaging.
Serial Settings: You may view the reserved RS-485 communication parameters here, and you may
set the timeout value for breaks in RS-485 communication. Note that the other serial communication
parameters cannot be modified. If you wish to adjust the baudrate, you will need to use the physical
dial on the back panel of the ioLogik E2210.
Web Access Settings: This field enables and disables the ioLogik E2210’s web console. The web
console allows the configuration of many settings using a web browser that is directed to the server’s
IP address. If the web console is not enabled in this field, you will not be able to access the web
console.
3-16
ioLogik E2210 User’s Manual
Using ioAdmin
Firmware Update Tab
The ioLogik E2210 supports remote firmware updates through the Firmware Update tab. Enter the
path to the firmware file or click on the icon to browse for the file. Click Update to update the
firmware. The wizard will lead you through the process until the server is restarted.
WARNING
Do not interrupt the firmware update process! An interruption in the process may result in
your device becoming unrecoverable.
After the firmware is updated, the ioLogik will restart and you will have to log in again to access
administrator functions.
The firmware on any attached I/O expansion module, such as an ioLogik R2000 server, must be
updated over the RS-485 bus. Firmware on cascaded modules cannot be updated over Ethernet.
Watchdog Tab
The Watchdog tab is where you configure the Host Connection Watchdog, which is used with the
Safe Status settings to define each DI/O channel’s response to a lost network connection. When the
ioLogik E2210 loses its network connection for the amount of time specified in the timeout, the Host
Connection Watchdog will switch the ioLogik E2210 to Safe Status and the DI/O channels will reset
to their Safe Status settings. By default, the Watchdog is disabled. To enable the Watchdog, make
sure Enable Host Connection Watchdog is checked, set the Timeout value, then click the Update
button.
3-17
ioLogik E2210 User’s Manual
Using ioAdmin
After the Watchdog is enabled, the ioLogik E2210 will enter safe status if the network connection is
lost. Once the connection has been restored, you will need to return to the Watchdog Tab in order to
exit safe status. There will be a message saying “Host Connection Lost”, indicating that the server is
in safe status. Click Clear Alarm to exit safe status and return to normal operation.
Click&Go Logic Tab
The Click&Go Logic tab is where administrators set up the ioLogik E2210’s active I/O messaging
program. Instead of the server reacting passively to repeated polling request from a host for I/O data,
the ioLogik E2210 is able to actively send I/O information to the host when an I/O channel satisfies
conditions that you specify. Click&Go Logic was developed by Moxa to provide a powerful and
easy-to-use tool for defining the conditions under which I/O information will be sent over the
network. Please refer to Click&Go V2 User’s Manual for more detailed information.
Changes made in the Click&Go Logic tab are not effective until the ioLogik E2210 is restarted, just
like changes made in other tabs. Note that when Click&Go Logic is being used, the range and units
of I/O channel being used in Click&Go Logic may not be modified.
3-18
ioLogik E2210 User’s Manual
Using ioAdmin
Active Tags Tab
When logged in as an administrator, fill in the IP address in the Active Tags tab to configure
Active OPC Address and Port settings. ioLogik Active Ethernet I/O can support up to 5 IPs at the
same time. The Active OPC Server Address can be filled in using the IP address. The default port
number is 9900. The port number should be the same as the setting in Active OPC Server’s
“Active Tag Listen Port”. After the OPC setting and Channel Tags have been configured as desired,
click Create Tags. The ioLogik Active Ethernet I/O will reboot in order for the settings to take
effect.
These Tags depend
on the model
The Heartbeat Interval is the time between each instance Active OPC server is informed that
ioLogik is still working. The tags for Analog Value, such as AI, AO, RTD, TC, are synchronized
with pre-defined percentages that are filled in the On Change column. The updated DI/DO/Relay
tags can be synchronized by changing the status. If counter mode is used, Advanced Settings
allows you to synchronize time by 100 to 60,000 ms. Please refer to the Active OPC Server section
for more details about how to use Active OPC server.
3-19
ioLogik E2210 User’s Manual
Using ioAdmin
SNMP Settings Tab
The ioLogik Ethernet I/O supports SNMP V1, V2c, and V3 (Simple Network Management
Protocol) to monitor network and I/O devices with SNMP Network Management software. It is
useful in building automation and telecom applications. Use these fields to enable SNMP and set
the read and write community strings for SNMP V1 and V2c, or use authentication for SNMP V3.
Server Context Menu
The server context menu is accessed by right clicking on the server model name in the navigation
panel.
Connect
Select this command to have ioAdmin attempt a re-connection over the network to the selected
ioLogik server.
Disconnect
Select this command to have ioAdmin drop the network connection with the selected ioLogik server.
3-20
ioLogik E2210 User’s Manual
Using ioAdmin
Delete I/O Server
Select this command to have ioAdmin remove the selected server.
Add Serial I/O Server
Select this command to manually add a server by using its Unit ID.
Restart System
Select this command to restart your ioLogik E2210 from a remote site. You will need to log in as an
administrator to use this function.
Reset to Default
Select this command to reset all settings, including console password, to factory default values. You
will need to log in as an administrator to use this function.
Export System Config
Select this command to export the configuration of the ioLogik E2210 to a text file. You will need to
log in as an administrator to use this function. It is strongly recommended you use this method to
back up your configuration after you have finished configuring the ioLogik E2210 for your
application.
Below is an example of the exported configuration file.
Import System Config
Select this command to reload a configuration that was exported to a text file. You will need to log in
as an administrator to use this function. You will need to restart the ioLogik E2210 in order for the
new configuration to take effect. This command may be used to restore a configuration after loading
the factory defaults, or to duplicate a configuration to multiple ioLogik servers.
3-21
ioLogik E2210 User’s Manual
Using ioAdmin
Using TFTP to Import/Export Configuration
TFTP (Trivial File Transfer Protocol) was defined in 1980 to provide basic FTP functionality in a
very simple protocol. Due to TFTP’s simplicity, it can be implemented using a very small amount of
memory, an important consideration when it was first developed. ioLogik E2000 I/O servers support
the use of TFTP to import or export configuration files.
The following is an example using Windows TFTP and an ioLogik E2210 with an IP address of
192.168.127.254:
1. Enter “TFTP 192.168.127.254 GET ik2210.txt” to get the ioLogik’s configuration file.
2. Enter “TFTP 192.168.127.254 PUT ik2210.txt” to load a configuration file onto the ioLogik.
You must use “ik2210.txt” as the destination filename when copying a configuration file to the
ioLogik E2000 unit. Otherwise, you will receive an error message as shown below:
You can use TFTP in a batch file to transfer configuration files for different units. For example, you
might have two configuration files that need to be copied to two different servers: ik2210_1.txt for
192.168.127.253, and ik2210_2.txt for 192.168.127.254. A batch file could be written as follows:
tftp 192.168.127.253 put ik2210_1.txt ik2210.txt
tftp 192.168.127.254 put ik2210_2.txt ik2210.txt
ATTENTION
You can also run TFTP client software, open the configuration file, and enter the remote server’s
IP. Note that both ASCII and Octet mode are supported. When the download process is complete,
the I/O server will reboot.
WinTFTP Client Pro is a trademark of WinTFTP. All rights reserved.
3-22
ioLogik E2210 User’s Manual
Using ioAdmin
Using ioEventLog
Installing ioEventLog
ioEventLog is a Windows utility that can be used anywhere on the network to monitor the ioLogik
E2210.
1. Installation from CD: Insert the Document and Software CD into the host computer. Run
SETUP.EXE, which is located in the root directory. The installation program will guide you
through the installation process and install the ioEventLog utility.
2. Open ioEventLog: After installation is finished, run ioEventLog from Start Æ Program Files
Æ MOXA Æ IO Server Æ Utility Æ ioEventLog.
Basic Functions
ioEventLog is installed along with ioAdmin from the Document and Software CD. It is designed to
help you keep a record of ioLogik status events over the network. The log is stored on the Windows
PC. You will need to set up your ioLogik server to send status events to the PC’s IP address. The
following events are monitored:
y cold start
y warm start
For each event, the following information is provided. The log can be sorted by any of these fields:
y Event type
y Event date and time
y ioLogik server source name
y Source IP
y Destination IP
y Host date and time
y Source model
3-23
ioLogik E2210 User’s Manual
Using ioAdmin
Configuration
In the System menu, select Settings to configure ioEventLog.
The Alarm Listen Port is the TCP port number that will be monitored for status events. You can
modify this setting as necessary to receive signals through a firewall. It will need to match the
settings for the ioLogik server that is being monitored.
The Log Directory is where the log files will be stored. The default directory is C:\Program
Files\Moxa\ioEventLog\log. A separate log file is created for each day, with file names assigned
automatically.
You can also select the color of each event type in the log.
3-24
ioLogik E2210 User’s Manual
Using ioAdmin
Checking Connected Devices
You can see which I/O servers are already connected to ioEventLog by selecting Connected Device
List from the Connection menu.
Opening Log Files
You can view previously saved logs by selecting Open from the Log menu. You will be prompted for
the data that you wish to view.
The logs for the selected day will be displayed.
Clearing the Log
If you wish to clear the log, you can select Clear from Log menu. This will clear all events for the
current day. The cleared events will not be saved in that day’s logs. After the logs are cleared, new
events will be displayed and recorded as usual.
3-25
4
Chapter 4.
Using the Web Console
You may use the ioLogik E2210’s built in web console to configure many options.
The following topics are covered:
‰
‰
‰
‰
‰
‰
‰
‰
‰
Introduction to the Web Console
Basic Settings
Network Settings
¾ General Settings
¾ Ethernet Configuration
¾ RS-485 Settings
I/O Settings
¾ DI Channels
¾ DO Channels
System Management
¾ Accessible IP Settings
¾ SNMP Agent
¾ Network Connection
¾ Firmware Update
¾ Import System Config
¾ Export System Config
LCM
Change Password
Load Factory Default
Save/Restart
ioLogik E2210 User’s Manual
Using the Web Console
Introduction to the Web Console
The ioLogik E2210 web console is a browser-based configuration utility. When the ioLogik E2210
is connected to your network, you may enter the server’s IP address in your web browser to access
the web console. Note that although most configuration options are available in the web console,
some settings are only available through ioAdmin. Furthermore, the web console can be disabled
under Web Access Settings in ioAdmin. If you are unable to access the web console, check the Web
Access Settings in ioAdmin.
Main
Window
Navigation
Panel
The left panel is the navigation panel and contains an expandable menu tree for navigating among
the various settings and categories. When you click on a menu item in the navigation panel, the main
window will display the corresponding options for that item. Configuration changes can then be
made in the main window. For example, if you click on Basic Settings in the navigation panel, the
main window will show a page of basic settings that you can configure.
You must click on the Submit button after making configuration changes. The Submit button will
be located at the bottom of every page that has configurable settings. If you navigate to another page
without clicking the Submit button, your changes will not be retained.
Submitted changes will not take effect until they are saved and the ioLogik E2210 is restarted!
You may save and restart the server in one step by clicking on the Save/Restart button after you
submit a change. If you need to make several changes before restarting, you may save your changes
without restarting by selecting Save/Restart in the navigation panel. If you restart the ioLogik
E2210 without saving your configuration, the ioLogik E2210 will discard all submitted changes.
4-2
ioLogik E2210 User’s Manual
Using the Web Console
Basic Settings
On the Basic Settings page, you may set the ioLogik E2210’s system time or provide the IP address
of a time server for time synchronization.
Network Settings
General Settings
On the General Settings page, you may assign a server name and location to assist you in
differentiating between different I/O servers. You may also enable the Host Communication
Watchdog and define the timeout value.
The Host Connection Watchdog activates Safe Status when the ioLogik E2210 loses its network
connection for the specified amount of time. By default, the Watchdog is disabled. When the
Watchdog is enabled and a timeout occurs, the ioLogik E2210 will enter Safe Status. You may use
ioAdmin to configure how each DO channel responds in that channel’s Safe Status settings.
To enable the Watchdog, check off Enable connection watchdog, set the timeout value, and restart
the server. With Watchdog enabled, the ioLogik E2210 will enter Safe Status after there is disruption
in communication that exceeds the time specified.
4-3
ioLogik E2210 User’s Manual
Using the Web Console
Ethernet Configuration
On the Ethernet Configuration page, you may set up a static or dynamic IP address for the ioLogik
E2210, as well as the subnet mask and gateway address.
RS-485 Settings
On the RS-485 Settings page, you may view the serial communication parameters, but no
configuration changes are allowed. The baudrate may only be configured by the physical dial on the
back of the ioLogik E2210. This is a reserved function.
4-4
ioLogik E2210 User’s Manual
Using the Web Console
I/O Settings
DI Channels
On the DI Channels page, you may view the status of each DI (digital input) channel.
You may also configure each channel’s digital input mode and parameters by clicking on the channel.
DI channels can operate in DI mode or Event Counter mode.
For DI mode, the maximum value of the filter is 65535.
For Event Counter mode, you may configure the low width and high width in multiples of 0.5 ms.
The counter should be set to either start, or stop. If it is in stop mode, the counter can be activated
by the Modbus command. Make sure that the Counter Filter is not set to 0, otherwise the counter will
never be activated.
You may use the Power On Setting field to specify the channel’s setting when the ioLogik E2210 is
powered on, and the Safe Status Setting field to specify channel’s setting when the ioLogik E2210
enters Safe Status. Note that Safe Status is controlled by the Host Connection Watchdog, which is
disabled by default. If the Host Connection Watchdog is disabled, the ioLogik E2210 will never
enter Safe Status and your Safe Status settings will have no effect.
4-5
ioLogik E2210 User’s Manual
Using the Web Console
DO Channels
On the DO Channels page, you may configure each DO (digital output) channel by clicking on the
channel. DO Channels can operate in DO mode or Pulse Output mode. In DO mode, output is either
on or off. In Pulse Output mode, a configurable square wave is generated.
You may use the Power On Setting field to specify the channel’s setting when the ioLogik E2210 is
powered on, and the Safe Status Setting field to specify channel’s setting when the ioLogik E2210
enters Safe Status. Note that Safe Status is controlled by the Host Connection Watchdog, which is
disabled by default. If the Host Connection Watchdog is disabled, the ioLogik E2210 will never
enter Safe Status and your Safe Status settings will have no effect.
4-6
ioLogik E2210 User’s Manual
Using the Web Console
System Management
Accessible IP Settings
On the Accessible IP Settings page, you may control network access to the ioLogik E2210 by
allowing only specified IP addresses. When the accessible IP list is enabled, a host’s IP address must
be listed in order to have access to the ioLogik E2210.
You may add a specific address or range of addresses by using a combination of IP address and
netmask, as follows:
To allow access to a specific IP address
Enter the IP address in the corresponding field; enter 255.255.255.255 for the netmask.
To allow access to hosts on a specific subnet
For both the IP address and netmask, use 0 for the last digit (e.g., 192.168.1.0 and 255.255.255.0).
To allow unrestricted access
Deselect the Enable the accessible IP list option.
Refer to the following table for additional configuration examples.
Allowed Hosts
Any host
192.168.1.120
192.168.1.1 to 192.168.1.254
192.168.0.1 to 192.168.255.254
192.168.1.1 to 192.168.1.126
192.168.1.129 to 192.168.1.254
IP address/Netmask
Disable
192.168.1.120 / 255.255.255.255
192.168.1.0 / 255.255.255.0
192.168.0.0 / 255.255.0.0
192.168.1.0 / 255.255.255.128
192.168.1.128 / 255.255.255.128
4-7
ioLogik E2210 User’s Manual
Using the Web Console
SNMP Agent
On the SNMP Agent page, you may enable SNMP and set the read and write settings. The ioLogik
Ethernet I/O device supports SNMP v1, v2c, and V3 (Simple Network Management Protocol) to
allow monitoring of network and I/O devices with SNMP Network Management software. It is
useful in building automation and telecom applications. Use these fields to enable SNMP and set
the read and write community strings for SNMP v1 and v2c, or use authentication for SNMP v3.
Network Connection
On the Network Connection page, you may view the TCP connections from other hosts. This may
assist you in the management of your devices.
4-8
ioLogik E2210 User’s Manual
Using the Web Console
Firmware Update
On the Firmware Update page, you may load new or updated firmware onto the ioLogik.
Import System Config
On the Import System Config page, you may import a configuration onto the ioLogik server. The
configuration file can be generated by ioAdmin or through the web console. This function can be
used to duplicate settings between ioLogik servers. You will be prompted for the location of the
configuration file (i.e., “ik2210.txt”).
Export System Config
On the Export System Config page, you may save the ioLogik's configuration into a file for backup
or import into another ioLogik server.
4-9
ioLogik E2210 User’s Manual
Using the Web Console
LCM
If you have installed the optional LCM, you may view the status and firmware details on the LCM
page.
Change Password
For all changes to the ioLogik E2210’s password protection settings, you will first need to enter the
old password. Leave this blank if you are setting up password protection for the first time. To set up
a new password or change the existing password, enter your desired password under both New
password and Confirm password. To remove password protection, leave the New password and
Confirm password fields blank.
ATTENTION
If you forget the password, the ONLY way to configure the ioLogik E2210 is by using the reset
button to load the factory defaults.
Before you set a password for the first time, it is a good idea to export the configuration to a file
when you have finished setting up your ioLogik E2210. Your configuration can then be easily
imported back into the ioLogik E2210 if you need to reset the ioLogik E2210 due to a forgotten
password or for other reasons.
Load Factory Default
This function will reset all of the ioLogik E2210’s settings to the factory default values. All previous
settings including the console password will be lost.
Save/Restart
If you change the configuration, do not forget to reboot the system.
4-10
5
Chapter 5.
Active OPC Server Lite
In this chapter, we explain how to use ioAdmin to configure your ioLogik product.
The following topics are covered in this chapter:
‰
‰
‰
‰
‰
OLE for Process Control
Introduction to Active OPC Server Lite
Active OPC Server Lite – From Pull to Push
Features of Active OPC Server Lite
Active OPC Server Lite Specifications
¾ Installation of Active OPC Server Lite
¾ Installation of OPC Core Components
‰ Active OPC Server Lite
‰ Menu Items
¾ File
¾ System
¾ Sort
¾ Quick Links
‰ Tag Generation
¾ Push Tag Configuration from ioAdmin
¾ Advanced Settings
¾ Heartbeat Interval
¾ Read/Write Privilege
¾ OPC Test Client
ioLogik E2210 User’s Manual
Active OPC Server Lite
OLE for Process Control
OPC (originally OLE for process control) is an industry standard created with the collaboration of
a number of leading worldwide automation hardware and software suppliers, working in
cooperation with Microsoft. The standard defines methods for exchanging real-time automation
data between PC-based clients using Microsoft operating systems. The organization that manages
this standard is the OPC Foundation.
The OPC Specification is a non-proprietary technical specification that defines a set of standard
interfaces based upon Microsoft’s OLE/COM/DCOM platform and .NET technology. The
application of the OPC standard interface makes possible interoperability between
automation/control applications, field systems/devices and business/office applications.
Traditionally, each software or application developer was required to write a custom interface, or
server/driver, to exchange data with hardware field devices. OPC eliminates this requirement by
defining a common, high performance interface that permits this work to be done once, and then
easily reused by HMI, SCADA, Control and custom applications.
[Drivers must be installed several times to connect to different devices]
[OPC Client/Server creates a common interface connecting to different devices]
Introduction to Active OPC Server Lite
Moxa Active OPC Server Lite is a software package operated as an OPC driver of an HMI or
SCADA system. It offers seamless connection from Moxa ioLogik series products to the SCADA
systems, including the most popular Wonderware, Citect, and iFix. Active OPC Server Lite meets
the latest standard of OPC DA3.0 that allows connections to various kinds of devices and host
OPC machines.
5-2
ioLogik E2210 User’s Manual
Active OPC Server Lite
Active OPC Server Lite – From Pull to Push
When first looking up the I/O divices’ Modbus table, users need to create one tag within 19 or
more steps including specifying the IP address, selection of the protocols, and define the data type.
The procedure is repeated over and over again until all the devices and tags are created. A
technician can expect to take 1 minute to create just one tag. But what if there are 400 tags in the
OPC system? Also, the more tags are used, the higher CPU loading will be taken.
The general OPC also requires the connected I/O devices to use fixed IP address, if there are
applications running on a public network (usually dynamic IPs) or portable measurements, there is
no way to connect to an I/O device using OPC. This architecture is also called “pull” technology
because the OPC server always polls the I/O devices from tag creation, IP connection and the tag
status update.
Moxa Active Ethernet I/O – ioLogik series products provide the I/O status report via TCP/UDP
message, e-mail or SNMP traps. These benefits have now expanded to the OPC technology.
Without asking any questions, even the IP address, settings of a tag are automatically created by
the ioLogik itself to notify which tag should be created. Users need only to launch the Active OPC
Server program, and those I/O channels selected by a user will be “pushed” from an ioLogik to
Active OPC Server.
5-3
ioLogik E2210 User’s Manual
Active OPC Server Lite
The “push” technology also includes the update for the tags. When the I/O the status changes,
there will be updates from the ioLogik to Active OPC Server Lite. Compared to constantly polling
(pull-based) the status, this feature efficiently reduces the network bandwidth usage and speeds up
the response time with event-driven, push-based status updates. At the same time, the heartbeat
function visual confirms that ioLogik is “alive” and working.
Features of Active OPC Server Lite
Automatic tag generation
Without specifying IP addresses, I/O channels, and data formats one by one or editing and
importing any configuration text files, Active OPC Server Lite creates the tags for the target
ioLogik automatically. These tags are not fixed but created by users. After selecting the channels
required to be update to Active OPC Server Lite, it will generate the tag configuration without
asking any questions. Training for installation and configuration should be required to implement a
general OPC Server package. For ioLogik users, learning the OPC technology, looking up Modbus
address, configuring data format, assigning target IP and so on are not required.
Active tag update with heartbeat detection
ioLogik uses “Active” technology to update the I/O status. This includes the tag status update to
Active OPC Server Lite. Compared to traditional OPC Servers, this mechanism reduces Ethernet
bandwidth usage by 80%. At the same time, it increases the response time of the I/O channels 7
timers faster than before. The SCADA PC can now also be load balanced for its CPU time because
it simply waits for updates instead of polling the I/O channel all the time.
5-4
ioLogik E2210 User’s Manual
Active OPC Server Lite
Dynamic IP Address Support
Active OPC Server also delivers the flexibility of using dynamic IP addresses on the ioLogik. As
for the traditional data acquisition application, I/O devices are not capable of using this approach.
The flexibility of connections through firewall is also expanded.
Active OPC Server Lite Specifications
Hardware Requirements
CPU
RAM
Network Interface
Intel Pentium (Pentium 4 and above)
512 MB (1024 MB recommended)
10/100Mb Ethernet
Software Requirements
Operating System
Editor (Not necessary)
Microsoft Windows 2000, XP or later
Microsoft Office 2003 (Access 2003) or later
OPC Server Specifications
OPC Data Access
Max. tags
ioLogik Support
Product Model
Firmware version
ioAdmin version
1.0a, 2.0, 2.05a, 3.0
256
ioLogik E2210, E2212, E2214, E2240, E2242, E2260, E2262
V3.0 or above
V3.0 or above
Installation of Active OPC Server Lite
Active OPC Server Lite can be found in the Document and Software CD, or downloaded from
Moxa Website. The following steps show how to install Active OPC Server Lite from the CD.
1. Installation from CD: Insert the Document and Software CD into the host computer. In the
Software\AOPCLite directory of the CD, locate and run SETUP.EXE. The installation program
will guide you through the installation process and install the Active OPC Server Lite utility.
2. Open Active OPC Server Lite: After installation is finished, run Active OPC Server Lite from
the Windows Start menu: Start ÆProgram Files ÆMOXA ÆIO Server
ÆActiveOPCÆActiveOPC.
Installation of OPC Core Components
OPC Core Components provides the necessary connection library of Active OPC Server Lite. This
package must be installed in the computer where Active OPC Server Lite is.
1. After Active OPC Server Lite installation is finished, run Setup OPC Core Components from
the Windows Start menu: Start ÆProgram Files ÆMOXA ÆIO
ServerÆActiveOPCÆSetup OPC Core Components
The installation program will guide you through the installation process.
5-5
ioLogik E2210 User’s Manual
Active OPC Server Lite
Active OPC Server Lite
Main Screen Overview
Active OPC Server Lite’s main screen displays a figure of the mapped ioLogik with the status of
every I/O tag. Note that configuration and tags are not available until you have the ioLogik to create
the tags.
1
2
3
4
5
6
7
1
Active OPC Server Lite Main Screen
1. Title
2. Menu bar
3. Quick link
4. Navigation panel
5. Tag Window
6. Log Monitor
7. Status bar
5-6
ioLogik E2210 User’s Manual
Active OPC Server Lite
Menu Items
File
From the File menu, you can export the list of the ioLogik that are currently displayed in the
navigation panel. You also can import a list into Active OPC Server Lite.
The file will have .mdb extension and can be opened using Microsoft Office - Access. The server
list includes the current tag information of the mapped ioLogik. Saving the configuration when
exiting the Active OPC Server is also recommended.
System
Several operations can be accessed from the System menu.
Network Interface allows you to select a network to use, if the PC has multiple network adaptors
installed.
Active Tag Listen Port allows you to select the preferred TCP socket port for tag generation from
ioAdmin.
Stop Listen allows you to stop getting tag generation messages and I/O status updates.
Register OPC Server is used to register the DCOM components to the Windows system. After
Active OPC Server Lite is installed, it will automatically configure the DCOM.
5-7
ioLogik E2210 User’s Manual
Active OPC Server Lite
Unregister OPC Server is used to cancel the registration of the DCOM components from the
Windows system.
Sort
The Sort menu allows the server list in the navigation panel to be sorted by connection and type
(model).
Quick Links
Quick links are provided to sort the server list and import/export configuration.
Sort by connection
Sort by server type
Import configuration
Export configuration
Tag Generation
Push Tag Configuration from ioAdmin
Tag configuration of an ioLogik is specified by ioAdmin configuration utility. Start the ioAdmin,
log in as an administrator and go to the Active Tags.
5-8
ioLogik E2210 User’s Manual
Active OPC Server Lite
Following are the steps to create the tags.
1.
Click on the Set OPC Server Address (
Server Lite.
2.
Click Yes to restart the ioLogik.
5-9
) button to specify the IP address of Active OPC
ioLogik E2210 User’s Manual
Active OPC Server Lite
3.
Specify the channels needed to be monitored by Active OPC Server Lite.
4.
Click on the Create Tags button to push the tag configuration to Active OPC Server Lite.
5.
Start the Active OPC Server Lite from Windows Start Menu. In the log monitor, a message
will appear to confirm that the configuration was received. After that, tags are automatically
created.
Advanced Settings
Advanced settings of the tags define the period that an ioLogik checks for the counter input status.
By default, the status is checked as soon as it changes. Users can define the interval starting from
100 ms to 60 seconds.
5-10
ioLogik E2210 User’s Manual
Active OPC Server Lite
Heartbeat Interval
Tags are event-driven and updated only when the status of an I/O channel changes, so when the
status remains unchanged, there will not be an update to Active OPC Server Lite. To ensure the
ioLogik is connected and alive, Heartbeat Interval can be used to determine the connection status
between the ioLogik and Active OPC Server Lite. If the heartbeat interval is set and the network
between the ioLogik and Active OPC Server Lite is down, Active OPC Server Lite will detect the
stop of the heartbeat and the Quality column will show BAD to indicate the loss of the connection.
Default interval is set to 0 seconds, which disables the heartbeat. The maximum interval is 65,535
seconds.
Read/Write Privilege
An input channel can only be read while an output channel is read/write acceptable showing on the
Active OPC Server Lite. Note that if an output channel has been used in the Click&Go logic, the
tags for that channel are read-only.
OPC Test Client
An OPC client software is embedded into the Active OPC Server Lite package for test purposes.
After configuring the tags on the Active OPC Server Lite, this ClientTest can be launched from
the Windows Start menu: Start ÆProgram Files ÆMOXA ÆIO Server
ÆActiveOPCÆClientTest.
If Active OPC Server Lite is installed locally in the same PC, select Connect Æ Local from the
menu bar. Specify the MOXA ACTIVE OPC SERVER in the Server Name column.
5-11
ioLogik E2210 User’s Manual
Active OPC Server Lite
If the Active OPC Server Lite is installed on a remote PC, select Connect Æ Remote from the
menu bar. Input the host name (i.e. Moxa_Client) or IP address and specify MOXA ACTIVE
OPC SERVER in the Server Name column.
Click on the Group Æ Add and specify the Group Name (user-defined). A blank tag monitoring
screen will start.
5-12
ioLogik E2210 User’s Manual
Active OPC Server Lite
Click Item Æ Browse and select the channel needed to be monitored.
5-13
ioLogik E2210 User’s Manual
Active OPC Server Lite
To write to the output channel, specify an output channel first. Then, select Item Æ Write from
the menu bar.
5-14
A
Appendix A.
Liquid Crystal Display Module (LCM)
The ioLogik E2210 supports an optional detachable Liquid Crystal Display Module (LCM) for
easier field maintenance. The LCM is hot-pluggable and can be used to configure the network
settings or display other settings. When plugged in, the LCM displays the ioLogik E2210 “home
page,” and pressing any button takes you into the settings and configuration.
LCM Controls
The up and down buttons navigate between the current options. The right and left buttons enter and
exit the submenus. The center button is used when modifying settings or restarting the server.
Button
Up
Down
Function
Go to the previous item
Go to the next item
Left
Exit the current submenu and return to the previous menu (go up one level)
Right
Enter the selected submenu (go down one level)
Center
Enter/exit editing mode
An “e” in the upper right hand corner of the display indicates that the parameter can be modified.
Press the center button on the LCM to modify that parameter’s settings.
LCM Options
Display
<ioLogik E2210>
<ioLogik E2210>
server
Explanation / Actions
This is the default “home page” showing the IP address. Press
the down button to view the submenus.
Enter this submenu to display information about the specific
server you are viewing:
y serial number
y name
y location
y E2210 f/w ver
y lcm f/w ver
y model name
ioLogik E2210 User’s Manual
Display
<ioLogik E2210>
network
Liquid Crystal Display Module (LCM)
Explanation / Actions
Enter this submenu to display information and settings for the
network:
y Ethernet link
y MAC address
y IP mode
y IP address
y netmask
y gateway
y DNS server-1
y DNS server-2
<ioLogik E2210>
click&go
Enter this submenu to display information about the ruleset
being used by the active I/O system.
y name
y status
<ioLogik E2210>
serial port
Enter this submenu to display the RS-485 cascade port settings.
<ioLogik E2210>
i/o setting
<ioLogik E2210>
console
<ioLogik E2210>
ping
<ioLogik E2210>
save/restart
Enter this submenu to access I/O channel status. Here are
examples of settings that you might see:
y DI-00 [di]=off
y DO-00 [pulse]=stop
Press up or down to navigate through the different I/O channels
without having to go back to the previous menu.
Enter this submenu to see if the web console is enabled or
disabled.
Select this option to enter an IP address to ping. If you get a
“timeout” error, it indicates that the E2210 cannot reach that IP
address. Otherwise, the display will show the response time.
Enter this submenu to display the restart now submenu. Enter
the restart now submenu to display the restart option. Press
the center button to modify this option, then select enable to
save changes and reboot the I/O server. The disable option has
no effect.
WARNING
Any configuration changes that are made through the LCM will not take effect until the ioLogik
E2210 is restarted.
A-2
B
Appendix B.
Modbus/TCP Address Mappings
E2210 Modbus Mapping
0xxxx Read/Write Coils (Functions 1, 5, 15)
Reference
00001
00002
00003
00004
00005
00006
00007
00008
00009
00010
00011
00012
00013
00014
00015
00016
00017
00018
00019
00020
00021
00022
00023
00024
00025
00026
00027
00028
00029
00030
00031
00032
00033
Address
0x0000
0x0001
0x0002
0x0003
0x0004
0x0005
0x0006
0x0007
0x0008
0x0009
0x000A
0x000B
0x000C
0x000D
0x000E
0x000F
0x0010
0x0011
0x0012
0x0013
0x0014
0x0015
0x0016
0x0017
0x0018
0x0019
0x001A
0x001B
0x001C
0x001D
0x001E
0x001F
0x0020
Data Type
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
Description
CH0 DO Value 0: Off 1: On
CH1 DO Value 0: Off 1: On
CH2 DO Value 0: Off 1: On
CH3 DO Value 0: Off 1: On
CH4 DO Value 0: Off 1: On
CH5 DO Value 0: Off 1: On
CH6 DO Value 0: Off 1: On
CH7 DO Value 0: Off 1: On
CH0 DO Power On Value 0: Off 1: On
CH1 DO Power On Value 0: Off 1: On
CH2 DO Power On Value 0: Off 1: On
CH3 DO Power On Value 0: Off 1: On
CH4 DO Power On Value 0: Off 1: On
CH5 DO Power On Value 0: Off 1: On
CH6 DO Power On Value 0: Off 1: On
CH7 DO Power On Value 0: Off 1: On
CH0 DO Safe Value 0: Off 1: On
CH1 DO Safe Value 0: Off 1: On
CH2 DO Safe Value 0: Off 1: On
CH3 DO Safe Value 0: Off 1: On
CH4 DO Safe Value 0: Off 1: On
CH5 DO Safe Value 0: Off 1: On
CH6 DO Safe Value 0: Off 1: On
CH7 DO Safe Value 0: Off 1: On
CH0 DO Pulse Operate Status 0: Off 1: On
CH1 DO Pulse Operate Status 0: Off 1: On
CH2 DO Pulse Operate Status 0: Off 1: On
CH3 DO Pulse Operate Status 0: Off 1: On
CH4 DO Pulse Operate Status 0: Off 1: On
CH5 DO Pulse Operate Status 0: Off 1: On
CH6 DO Pulse Operate Status 0: Off 1: On
CH7 DO Pulse Operate Status 0: Off 1: On
CH0 DI Pulse Operate Status 0: Off 1: On
ioLogik E2210 User’s Manual
Modbus/TCP Address Mappings
00034
00035
00036
00037
00038
00039
00040
00041
00042
00043
00044
00045
0x0021
0x0022
0x0023
0x0024
0x0025
0x0026
0x0027
0x0028
0x0029
0x002A
0x002B
0x002C
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
00046
0x002D
1 bit
00047
0x002E
1 bit
00048
0x002F
1 bit
00049
0x0030
1 bit
00050
0x0031
1 bit
00051
0x0032
1 bit
00052
0x0033
1 bit
00053
0x0034
1 bit
00054
0x0035
1 bit
00055
0x0036
1 bit
00056
0x0037
1 bit
00057
0x0038
1 bit
CH1 DI Pulse Operate Status 0: Off 1: On
CH2 DI Pulse Operate Status 0: Off 1: On
CH3 DI Pulse Operate Status 0: Off 1: On
CH4 DI Pulse Operate Status 0: Off 1: On
CH5 DI Pulse Operate Status 0: Off 1: On
CH6 DI Pulse Operate Status 0: Off 1: On
CH7 DI Pulse Operate Status 0: Off 1: On
CH8 DI Pulse Operate Status 0: Off 1: On
CH9 DI Pulse Operate Status 0: Off 1: On
CH10 DI Pulse Operate Status 0: Off 1: On
CH11 DI Pulse Operate Status 0: Off 1: On
CH0 DI Clear Count Value Read always :0
Write: 1 : Clear counter value
0 : return Illegal Data Value
CH1 DI Clear Count Value Read always :0
Write: 1 : Clear counter value
0 : return Illegal Data Value
CH2 DI Clear Count Value Read always :0
Write: 1 : Clear counter value
0 : return Illegal Data Value
CH3 DI Clear Count Value Read always :0
Write: 1 : Clear counter value
0 : return Illegal Data Value
CH4 DI Clear Count Value Read always :0
Write: 1 : Clear counter value
0 : return Illegal Data Value
CH5 DI Clear Count Value Read always :0
Write: 1 : Clear counter value
0 : return Illegal Data Value
CH6 DI Clear Count Value Read always :0
Write: 1 : Clear counter value
0 : return Illegal Data Value
CH7 DI Clear Count Value Read always :0
Write: 1 : Clear counter value
0 : return Illegal Data Value
CH8 DI Clear Count Value Read always :0
Write: 1 : Clear counter value
0 : return Illegal Data Value
CH9 DI Clear Count Value Read always :0
Write: 1 : Clear counter value
0 : return Illegal Data Value
CH10 DI Clear Count Value Read always :0
Write: 1 : Clear counter value
0 : return Illegal Data Value
CH11 DI Clear Count Value Read always :0
Write: 1 : Clear counter value
0 : return Illegal Data Value
CH0 DI OverFlow Status Read : 0 : Normal
1 : Overflow
Write : 0 : clear overflow status
B-2
ioLogik E2210 User’s Manual
Modbus/TCP Address Mappings
00058
0x0039
1 bit
00059
0x003A
1 bit
00060
0x003B
1 bit
00061
0x003C
1 bit
00062
0x003D
1 bit
00063
0x003E
1 bit
00065
0x003F
1 bit
00066
0x0040
1 bit
00067
0x0041
1 bit
00068
0x0042
1 bit
00069
0x0043
1 bit
00069
00070
00071
00072
00073
00074
0x0044
0x0045
0x0046
0x0047
0x0048
0x0049
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 : return Illegal Data Value
CH1 DI OverFlow Status Read : 0 : Normal
1 : Overflow
Write : 0 : clear overflow status
1 : return Illegal Data Value
CH2 DI OverFlow Status Read : 0 : Normal
1 : Overflow
Write : 0 : clear overflow status
1 : return Illegal Data Value
CH3 DI OverFlow Status Read : 0 : Normal
1 : Overflow
Write : 0 : clear overflow status
1 : return Illegal Data Value
CH4 DI OverFlow Status Read : 0 : Normal
1 : Overflow
Write : 0 : clear overflow status
1 : return Illegal Data Value
CH5 DI OverFlow Status Read : 0 : Normal
1 : Overflow
Write : 0 : clear overflow status
1 : return Illegal Data Value
CH6 DI OverFlow Status Read : 0 : Normal
1 : Overflow
Write : 0 : clear overflow status
1 : return Illegal Data Value
CH7 DI OverFlow Status Read : 0 : Normal
1 : Overflow
Write : 0 : clear overflow status
1 : return Illegal Data Value
CH8 DI OverFlow Status Read : 0 : Normal
1 : Overflow
Write : 0 : clear overflow status
1 : return Illegal Data Value
CH9 DI OverFlow Status Read : 0 : Normal
1 : Overflow
Write : 0 : clear overflow status
1 : return Illegal Data Value
CH10 DI OverFlow Status Read : 0 : Normal
1 : Overflow
Write : 0 : clear overflow status
1 : return Illegal Data Value
CH11 DI OverFlow Status Read : 0 : Normal
1 : Overflow
Write : 0 : clear overflow status
1 : return Illegal Data Value
CH0 DI Count Trigger
CH1 DI Count Trigger
CH2 DI Count Trigger
CH3 DI Count Trigger
CH4 DI Count Trigger
CH5 DI Count Trigger
B-3
ioLogik E2210 User’s Manual
00075
00076
00077
00078
00079
00070
0x004A
0x004B
0x004C
0x004D
0x004E
0x004F
Modbus/TCP Address Mappings
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
CH6 DI Count Trigger
CH7 DI Count Trigger
CH8 DI Count Trigger
CH9 DI Count Trigger
CH10 DI Count Trigger
CH11 DI Count Trigger
1xxxx Read Only Coils (Function 2)
Reference
10001
10002
10003
10004
10005
10006
10007
10008
10009
10010
10011
10012
Address
0x0000
0x0001
0x0002
0x0003
0x0004
0x0005
0x0006
0x0007
0x0008
0x0009
0x000A
0x000B
Data Type
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
Description
CH0 DI Value
CH1 DI Value
CH2 DI Value
CH3 DI Value
CH4 DI Value
CH5 DI Value
CH6 DI Value
CH7 DI Value
CH8 DI Value
CH9 DI Value
CH10 DI Value
CH11 DI Value
3xxxx Read Only Registers (Function 4)
Reference
30001
30002
30003
30004
30005
30006
30007
30008
30009
30010
30011
30012
30013
30014
30015
30016
30017
30018
30019
30020
30021
30022
30023
Address
0x0000
0x0001
0x0002
0x0003
0x0004
0x0005
0x0006
0x0007
0x0008
0x0009
0x000A
0x000B
0x000C
0x000D
0x000E
0x000F
0x0010
0x0011
0x0012
0x0013
0x0014
0x0015
0x0016
Data Type
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
B-4
Description
CH0 DI Count Value Hi-Byte
CH0 DI Count Value Lo-Byte
CH1 DI Count Value Hi-Byte
CH1 DI Count Value Lo-Byte
CH2 DI Count Value Hi-Byte
CH2 DI Count Value Lo-Byte
CH3 DI Count Value Hi-Byte
CH3 DI Count Value Lo-Byte
CH4 DI Count Value Hi-Byte
CH4 DI Count Value Lo-Byte
CH5 DI Count Value Hi-Byte
CH5 DI Count Value Lo-Byte
CH6 DI Count Value Hi-Byte
CH6 DI Count Value Lo-Byte
CH7 DI Count Value Hi-Byte
CH7 DI Count Value Lo-Byte
CH8 DI Count Value Hi-Byte
CH8 DI Count Value Lo-Byte
CH9 DI Count Value Hi-Byte
CH9 DI Count Value Lo-Byte
CH10 DI Count Value Hi-Byte
CH10 DI Count Value Lo-Byte
CH11 DI Count Value Hi-Byte
ioLogik E2210 User’s Manual
30024
0x0017
Modbus/TCP Address Mappings
word
CH11 DI Count Value Lo-Byte
// for Citect SCADA compatibility, I/O data can be WORD accessed as well
312289
312290
312291
312292
312293
312294
312295
312296
312297
312298
312299
312300
0x3000
0x3001
0x3002
0x3003
0x3004
0x3005
0x3006
0x3007
0x3008
0x3009
0x300A
0x300B
word
word
word
word
word
word
word
word
word
word
word
word
CH0 DI Value
CH1 DI Value
CH2 DI Value
CH3 DI Value
CH4 DI Value
CH5 DI Value
CH6 DI Value
CH7 DI Value
CH8 DI Value
CH9 DI Value
CH10 DI Value
CH11 DI Value
4xxxx Read/Write Registers (Functions 3, 6, 16)
Reference
40001
40002
40003
40004
40005
40006
40007
40008
40009
40010
40011
40012
40013
40014
40015
40016
40017
40018
40019
40020
40021
40022
40023
40024
40025
40026
40027
40028
40029
40030
40031
Address
0x0000
0x0001
0x0002
0x0003
0x0004
0x0005
0x0006
0x0007
0x0008
0x0009
0x000A
0x000B
0x000C
0x000D
0x000E
0x000F
0x0010
0x0011
0x0012
0x0013
0x0014
0x0015
0x0016
0x0017
0x0018
0x0019
0x001A
0x001B
0x001C
0x001D
0x001E
Data Type
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
Description
CH0 DO Pulse Output Count Value Hi-Byte
CH0 DO Pulse Output Count Value Lo-Byte
CH1 DO Pulse Output Count Value Hi-Byte
CH1 DO Pulse Output Count Value Lo-Byte
CH2 DO Pulse Output Count Value Hi-Byte
CH2 DO Pulse Output Count Value Lo-Byte
CH3 DO Pulse Output Count Value Hi-Byte
CH3 DO Pulse Output Count Value Lo-Byte
CH4 DO Pulse Output Count Value Hi-Byte
CH4 DO Pulse Output Count Value Lo-Byte
CH5 DO Pulse Output Count Value Hi-Byte
CH5 DO Pulse Output Count Value Lo-Byte
CH6 DO Pulse Output Count Value Hi-Byte
CH6 DO Pulse Output Count Value Lo-Byte
CH7 DO Pulse Output Count Value Hi-Byte
CH7 DO Pulse Output Count Value Lo-Byte
CH0 DO Pulse Low Signal Width
CH1 DO Pulse Low Signal Width
CH2 DO Pulse Low Signal Width
CH3 DO Pulse Low Signal Width
CH4 DO Pulse Low Signal Width
CH5 DO Pulse Low Signal Width
CH6 DO Pulse Low Signal Width
CH7 DO Pulse Low Signal Width
CH0 DO PulseHigh Signal Width
CH1 DO PulseHigh Signal Width
CH2 DO PulseHigh Signal Width
CH3 DO PulseHigh Signal Width
CH4 DO PulseHigh Signal Width
CH5 DO PulseHigh Signal Width
CH6 DO PulseHigh Signal Width
B-5
ioLogik E2210 User’s Manual
Modbus/TCP Address Mappings
40032
40033
0x001F
0x0020
word
word
40034
0x0021
word
40035
0x0022
word
40036
0x0023
word
40037
0x0024
word
40038
0x0025
word
40039
0x0026
word
40040
0x0027
word
40041
40042
40043
40044
40045
40046
40047
40048
40049
40050
40051
40052
40053
0x0028
0x0029
0x002A
0x002B
0x002C
0x002D
0x002E
0x002F
0x0030
0x0031
0x0032
0x0033
0x0034
word
word
word
word
word
word
word
word
word
word
word
word
word
40054
0x0035
word
40055
0x0036
word
40056
0x0037
word
40057
0x0038
word
40058
0x0039
word
40059
0x003A
word
CH7 DO PulseHigh Signal Width
CH0 DO Mode 0: DO
1: Pulse
CH1 DO Mode 0: DO
1: Pulse
CH2 DO Mode 0: DO
1: Pulse
CH3 DO Mode 0: DO
1: Pulse
CH4 DO Mode 0: DO
1: Pulse
CH5 DO Mode 0: DO
1: Pulse
CH6 DO Mode 0: DO
1: Pulse
CH7 DO Mode 0: DO
1: Pulse
CH0 DI Count Filter
CH1 DI Count Filter
CH2 DI Count Filter
CH3 DI Count Filter
CH4 DI Count Filter
CH5 DI Count Filter
CH6 DI Count Filter
CH7 DI Count Filter
CH8 DI Count Filter
CH9 DI Count Filter
CH10 DI Count Filter
CH11 DI Count Filter
CH0 DI Mode 0: DI
1: Count
Others : return Illegal Data Value
CH1 DI Mode 0: DI
1: Count
Others : return Illegal Data Value
CH2 DI Mode 0: DI
1: Count
Others : return Illegal Data Value
CH3 DI Mode 0: DI
1: Count
Others : return Illegal Data Value
CH4 DI Mode 0: DI
1: Count
Others : return Illegal Data Value
CH5 DI Mode 0: DI
1: Count
Others : return Illegal Data Value
CH6 DI Mode 0: DI
1: Count
Others : return Illegal Data Value
B-6
ioLogik E2210 User’s Manual
Modbus/TCP Address Mappings
40060
0x003B
word
40061
0x003C
word
40062
0x003D
word
40063
0x003E
word
40064
0x003F
word
40377
40378
40379
40380
40381
40382
40383
40384
40385
40386
40387
40388
40389
40390
40391
40392
40393
40394
40395
40396
40397
40398
40389
40390
40391
40392
40393
40394
40395
40396
40397
40398
40399
40400
0x0178
0x0179
0x017A
0x017B
0x017C
0x017D
0x017E
0x017F
0x0180
0x0181
0x0182
0x0183
0x0184
0x0185
0x0186
0x0187
0x0188
0x0189
0x018A
0x018B
0x018C
0x018D
0x0184
0x0185
0x0186
0x0187
0x0188
0x0189
0x018A
0x018B
0x018C
0x018D
0x018E
0x018F
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
word
CH7 DI Mode 0: DI
1: Count
Others : return Illegal Data Value
CH8 DI Mode 0: DI
1: Count
Others : return Illegal Data Value
CH9 DI Mode 0: DI
1: Count
Others : return Illegal Data Value
CH10 DI Mode 0: DI
1: Count
Others : return Illegal Data Value
CH11 DI Mode 0: DI
1: Count
Others : return Illegal Data Value
Internal Register 00 Value
Internal Register 01 Value
Internal Register 02 Value
Internal Register 03 Value
Internal Register 04 Value
Internal Register 05 Value
Internal Register 06 Value
Internal Register 07 Value
Internal Register 08 Value
Internal Register 09 Value
Internal Register 10 Value
Internal Register 11 Value
Internal Register 12 Value
Internal Register 13 Value
Internal Register 14 Value
Internal Register 15 Value
Internal Register 16 Value
Internal Register 17 Value
Internal Register 18 Value
Internal Register 19 Value
Internal Register 20 Value
Internal Register 21 Value
Internal Register 12 Value
Internal Register 13 Value
Internal Register 14 Value
Internal Register 15 Value
Internal Register 16 Value
Internal Register 17 Value
Internal Register 18 Value
Internal Register 19 Value
Internal Register 20 Value
Internal Register 21 Value
Internal Register 22 Value
Internal Register 23 Value
// for Citect SCADA compatibility, I/O data can be WORD accessed as well
B-7
ioLogik E2210 User’s Manual
Modbus/TCP Address Mappings
40257
40258
40259
40260
40261
40262
40263
40264
40265
40266
40267
40268
40269
40270
40271
40272
40273
40274
40275
40276
40277
40278
40279
40280
40281
40282
40283
40284
40285
40286
40287
40288
40289
0x0100
0x0101
0x0102
0x0103
0x0104
0x0105
0x0106
0x0107
0x0108
0x0109
0x010A
0x010B
0x010C
0x010D
0x010E
0x010F
0x0110
0x0111
0x0112
0x0113
0x0114
0x0115
0x0116
0x0117
0x0118
0x0119
0x011A
0x011B
0x011C
0x011D
0x011E
0x011F
0x0120
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
40290
0x0121
1 word
40291
0x0122
1 word
40292
0x0123
1 word
40293
0x0124
1 word
40294
0x0125
1 word
40295
0x0126
1 word
40296
0x0127
1 word
40297
0x0128
1 word
CH0 DO Value 0: Off 1: On
CH1 DO Value 0: Off 1: On
CH2 DO Value 0: Off 1: On
CH3 DO Value 0: Off 1: On
CH4 DO Value 0: Off 1: On
CH5 DO Value 0: Off 1: On
CH6 DO Value 0: Off 1: On
CH7 DO Value 0: Off 1: On
CH0 DO Power On Value 0: Off 1: On
CH1 DO Power On Value 0: Off 1: On
CH2 DO Power On Value 0: Off 1: On
CH3 DO Power On Value 0: Off 1: On
CH4 DO Power On Value 0: Off 1: On
CH5 DO Power On Value 0: Off 1: On
CH6 DO Power On Value 0: Off 1: On
CH7 DO Power On Value 0: Off 1: On
CH0 DO Safe Mode Value 0: Off 1: On
CH1 DO Safe Mode Value 0: Off 1: On
CH2 DO Safe Mode Value 0: Off 1: On
CH3 DO Safe Mode Value 0: Off 1: On
CH4 DO Safe Mode Value 0: Off 1: On
CH5 DO Safe Mode Value 0: Off 1: On
CH6 DO Safe Mode Value 0: Off 1: On
CH7 DO Safe Mode Value 0: Off 1: On
CH0 DO Pulse Operate Status 0: Stop 1: Start
CH1 DO Pulse Operate Status 0: Stop 1: Start
CH2 DO Pulse Operate Status 0: Stop 1: Start
CH3 DO Pulse Operate Status 0: Stop 1: Start
CH4 DO Pulse Operate Status 0: Stop 1: Start
CH5 DO Pulse Operate Status 0: Stop 1: Start
CH6 DO Pulse Operate Status 0: Stop 1: Start
CH7 DO Pulse Operate Status 0: Stop 1: Start
CH0 DO PowerOn Pulse Operate Status 0: Stop 1:
Start
CH1 DO PowerOn Pulse Operate Status 0: Stop 1:
Start
CH2 DO PowerOn Pulse Operate Status 0: Stop 1:
Start
CH3 DO PowerOn Pulse Operate Status 0: Stop 1:
Start
CH4 DO PowerOn Pulse Operate Status 0: Stop 1:
Start
CH5 DO PowerOn Pulse Operate Status 0: Stop 1:
Start
CH6 DO PowerOn Pulse Operate Status 0: Stop 1:
Start
CH7 DO PowerOn Pulse Operate Status 0: Stop 1:
Start
CH0 DO Safe Mode Pulse Operate Status 0: Stop 1:
Start
B-8
ioLogik E2210 User’s Manual
Modbus/TCP Address Mappings
40298
0x0129
1 word
40299
0x012A
1 word
40300
0x012B
1 word
40301
0x012C
1 word
40302
0x012D
1 word
40303
0x012E
1 word
40304
0x012F
1 word
40305
40306
40307
40308
40309
40310
40311
40312
40313
40314
40315
40316
40317
0x0130
0x0131
0x0132
0x0133
0x0134
0x0135
0x0136
0x0137
0x0138
0x0139
0x013A
0x013B
0x013C
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
1 word
40318
0x013D
1 word
40319
0x013E
1 word
40320
0x013F
1 word
40321
0x0140
1 word
40322
0x0141
1 word
40323
0x0142
1 word
40324
0x0143
1 word
CH1 DO Safe Mode Pulse Operate Status 0: Stop 1:
Start
CH2 DO Safe Mode Pulse Operate Status 0: Stop 1:
Start
CH3 DO Safe Mode Pulse Operate Status 0: Stop 1:
Start
CH4 DO Safe Mode Pulse Operate Status 0: Stop 1:
Start
CH5 DO Safe Mode Pulse Operate Status 0: Stop 1:
Start
CH6 DO Safe Mode Pulse Operate Status 0: Stop 1:
Start
CH7 DO Safe Mode Pulse Operate Status 0: Stop 1:
Start
CH0 DI Counter Operate Status 0: Stop 1: Start
CH1 DI Counter Operate Status 0: Stop 1: Start
CH2 DI Counter Operate Status 0: Stop 1: Start
CH3 DI Counter Operate Status 0: Stop 1: Start
CH4 DI Counter Operate Status 0: Stop 1: Start
CH5 DI Counter Operate Status 0: Stop 1: Start
CH6 DI Counter Operate Status 0: Stop 1: Start
CH7 DI Counter Operate Status 0: Stop 1: Start
CH8 DI Counter Operate Status 0: Stop 1: Start
CH9 DI Counter Operate Status 0: Stop 1: Start
CH10 DI Counter Operate Status 0: Stop 1: Start
CH11 DI Counter Operate Status 0: Stop 1: Start
CH0 DI Clear Count Value Read: always return: 0
Write: 1 : Clear counter value0 : Return illegal data
value(0x03)
CH1 DI Clear Count Value Read: always return: 0
Write: 1 : Clear counter value 0 : Return illegal data
value(0x03)
CH2 DI Clear Count Value Read: always return: 0
Write: 1 : Clear counter value 0 : Return illegal data
value(0x03)
CH3 DI Clear Count Value Read: always return: 0
Write: 1 : Clear counter value 0 : Return illegal data
value(0x03)
CH4 DI Clear Count Value Read: always return: 0
Write: 1 : Clear counter value 0 : Return illegal data
value(0x03)
CH5 DI Clear Count Value Read: always return: 0
Write: 1 : Clear counter value 0 : Return illegal data
value(0x03)
CH6 DI Clear Count Value Read: always return: 0
Write: 1 : Clear counter value 0 : Return illegal data
value(0x03)
CH7 DI Clear Count Value Read: always return: 0
Write: 1 : Clear counter value 0 : Return illegal data
value(0x03)
B-9
ioLogik E2210 User’s Manual
Modbus/TCP Address Mappings
40325
0x0144
1 word
40326
0x0145
1 word
40327
0x0146
1 word
40328
0x0147
1 word
40329
0x0148
1 word
40330
0x0149
1 word
40331
0x014A
1 word
40332
0x014B
1 word
40333
0x014C
1 word
40334
0x014D
1 word
40335
0x014E
1 word
40336
0x014F
1 word
40337
0x0150
1 word
40338
0x0151
1 word
CH8 DI Clear Count Value Read: always return:
0Write: 1 : Clear counter value 0 : Return illegal data
value(0x03)
CH9 DI Clear Count Value Read: always return:
0Write: 1 : Clear counter value 0 : Return illegal data
value(0x03)
CH10 DI Clear Count Value Read: always return:
0Write: 1 : Clear counter value 0 : Return illegal data
value(0x03)
CH11 DI Clear Count Value Read: always return: 0
Write: 1 : Clear counter value0 : Return illegal data
value(0x03)
CH0 DI OverFlow Status Read: 0 : Normal
1 : Overflow
Write : 0 : Clear overflow status
1 : Return illegal data value (0x03)
CH1 DI OverFlow Status Read: 0 : Normal
1 : Overflow
Write : 0 : Clear overflow status
1 : Return illegal data value (0x03)
CH2 DI OverFlow Status Read: 0 : Normal
1 : Overflow
Write : 0 : Clear overflow status
1 : Return illegal data value (0x03)
CH3 DI OverFlow Status Read: 0 : Normal
1 : Overflow
Write : 0 : Clear overflow status
1 : Return illegal data value (0x03)
CH4 DI OverFlow Status Read: 0 : Normal
1 : Overflow
Write : 0 : Clear overflow status
1 : Return illegal data value (0x03)
CH5 DI OverFlow Status Read: 0 : Normal
1 : Overflow
Write : 0 : Clear overflow status
1 : Return illegal data value (0x03)
CH6 DI OverFlow Status Read: 0 : Normal
1 : Overflow
Write : 0 : Clear overflow status
1 : Return illegal data value (0x03)
CH7 DI OverFlow Status Read: 0 : Normal
1 : Overflow
Write : 0 : Clear overflow status
1 : Return illegal data value (0x03)
CH8 DI OverFlow Status Read: 0 : Normal
1 : Overflow
Write : 0 : Clear overflow status
1 : Return illegal data value (0x03)
CH9 DI OverFlow Status Read: 0 : Normal
1 : Overflow
Write : 0 : Clear overflow status
B-10
ioLogik E2210 User’s Manual
Modbus/TCP Address Mappings
40339
0x0152
1 word
40340
0x0153
1 word
40341
0x0154
1 word
40342
0x0155
1 word
40343
0x0156
1 word
40344
0x0157
1 word
40345
0x0158
1 word
40346
0x0159
1 word
40347
0x015A
1 word
40348
0x015B
1 word
40349
0x015C
1 word
40350
0x015D
1 word
40351
0x015E
1 word
40352
0x015F
1 word
40353
0x0160
1 word
40354
0x0161
1 word
40355
0x0162
1 word
40356
0x0163
1 word
40357
0x0164
1 word
40358
0x0165
1 word
40359
0x0166
1 word
1 : Return illegal data value (0x03)
CH10 DI OverFlow Status Read: 0 : Normal
1 : Overflow
Write : 0 : Clear overflow status
1 : Return illegal data value (0x03)
CH11 DI OverFlow Status Read: 0 : Normal
1 : Overflow
Write : 0 : Clear overflow stat
1 : Return illegal data value (0x03)
CH0 DI Counter Trigger,0=Low to High, 1=High to
Low
CH1 DI Counter Trigger,0=Low to High, 1=High to
Low
CH2 DI Counter Trigger,0=Low to High, 1=High to
Low
CH3 DI Counter Trigger,0=Low to High, 1=High to
Low
CH4 DI Counter Trigger,0=Low to High, 1=High to
Low
CH5 DI Counter Trigger,0=Low to High, 1=High to
Low
CH6 DI Counter Trigger,0=Low to High, 1=High to
Low
CH7 DI Counter Trigger,0=Low to High, 1=High to
Low
CH8 DI Counter Trigger,0=Low to High, 1=High to
Low
CH9 DI Counter Trigger,0=Low to High, 1=High to
Low
CH10 DI Counter Trigger,0=Low to High, 1=High to
Low
CH11 DI Counter Trigger,0=Low to High, 1=High to
Low
CH0 DI PowerOn Counter Operate Status 0: Stop 1:
Start
CH1 DI PowerOn Counter Operate Status 0: Stop 1:
Start
CH2 DI PowerOn Counter Operate Status 0: Stop 1:
Start
CH3 DI PowerOn Counter Operate Status 0: Stop 1:
Start
CH4 DI PowerOn Counter Operate Status 0: Stop 1:
Start
CH5 DI PowerOn Counter Operate Status 0: Stop 1:
Start
CH6 DI PowerOn Counter Operate Status 0: Stop 1:
Start
B-11
ioLogik E2210 User’s Manual
Modbus/TCP Address Mappings
40360
0x0167
1 word
40361
0x0168
1 word
40362
0x0169
1 word
40363
0x016A
1 word
40364
0x016B
1 word
40365
0x016C
1 word
40366
0x016D
1 word
40367
0x016E
1 word
40368
0x016F
1 word
40369
0x0170
1 word
40370
0x0171
1 word
40371
0x0172
1 word
40372
0x0173
1 word
40373
0x0174
1 word
40374
0x0175
1 word
40375
0x0176
1 word
40376
0x0177
1 word
CH7 DI PowerOn Counter Operate Status 0: Stop 1:
Start
CH8 DI PowerOn Counter Operate Status 0: Stop 1:
Start
CH9 DI PowerOn Counter Operate Status 0: Stop 1:
Start
CH10 DI PowerOn Counter Operate Status 0: Stop 1:
Start
CH11 DI PowerOn Counter Operate Status 0: Stop 1:
Start
CH0 DI Safe Mode Counter Operate Status 0: Stop 1:
Start
CH1 DI Safe Mode Counter Operate Status 0: Stop 1:
Start
CH2 DI Safe Mode Counter Operate Status 0: Stop 1:
Start
CH3 DI Safe Mode Counter Operate Status 0: Stop 1:
Start
CH4 DI Safe Mode Counter Operate Status 0: Stop 1:
Start
CH5 DI Safe Mode Counter Operate Status 0: Stop 1:
Start
CH6 DI Safe Mode Counter Operate Status 0: Stop 1:
Start
CH7 DI Safe Mode Counter Operate Status 0: Stop 1:
Start
CH8 DI Safe Mode Counter Operate Status 0: Stop 1:
Start
CH9 DI Safe Mode Counter Operate Status 0: Stop 1:
Start
CH10 DI Safe Mode Counter Operate Status 0: Stop 1:
Start
CH11 DI Safe Mode Counter Operate Status 0: Stop 1:
Start
B-12
C
Appendix C.
Used Network Port Numbers
E2210 Network Port Usage
Port
80
502
161
68
68
4800
9020
69
9000
9000
9900
4040
Type
TCP
TCP
TCP
UDP
UDP
UDP
TCP
UDP
TCP
UDP
TCP
TCP
Usage
Web server
Modbus communication
SNMP
BOOTPC
DHCP
Auto search
Peer-to-Peer function
Export/import file
Active Message (default)
Active Message (default)
Active Tags updates (default)
ioEventLog
D
Appendix D.
SNMP MIB II
RFC1213 MIB II Supported SNMP Variables
The following SNMP variables are built into the ioLogik firmware and are compliant with
RFC1213 MIB II.
System MIB
SysDescr
SysName
SysObjectID
SysLocation
SysUpTime
SysContact
ifAdminStatus
ifInOctets
ifOperStatus
ifOutUcastPkts
ifDescr
ifInUcastPkts
ifOutDiscards
ifPhysAddress
ifIndex
ifInUnknownProtos
ifOutErrors
ifSpecific
ifInDiscards
ifLastChange
ifOutNUcastPkts
ifSpeed
ifInErrors
ifMtu
ifOutOctets
ifType
ifInNUcastPkts
ifNumber
ifOutQLen
ipAdEntAddr
ipFragOKs
IpNetToMediaType
ipRouteIfIndex
ipAdEntBcastAddr
ipInAddrErrors
ipOutDiscards
ipRouteInfo
ipAdEntIfIndex
ipInDelivers
ipOutNoRoutes
ipRouteMask
ipAdEntNetMask
ipInDiscards
ipAdEntReasmMaxSiz ipInHdrErrors
ipOutRequests
ipRouteMetric1
ipReasmFails
ipRouteMetric2
ipDefaultTTL
ipInreceives
ipReasmOKs
ipRouteMetric3
ipForwarding
ipInUnknownProtos
ipReasmReqds
ipRouteMetric4
ipForwDatagrams
IpNetToMediaIfIndex ipReasmTimeout
IpNetToMediaNetAddr ipRouteAge
IpNetToMediaPhysAdd ipRouteDest
Interfaces MIB
IP MIB
ipFragCreates
ipFragFails
ipRouteType
IpRoutingDiscards
ICMP MIB
ipRouteMetric5
ipRouteNextHop
ipRouteProto
ioLogik E2210 User’s Manual
Modbus/TCP Address Mappings
IP MIB
IcmpInAddrMasks
IcmpInRedirects
IcmpOutEchoReps
IcmpInDestUnreachs
IcmpInSrcQuenchs
IcmpOutEchos
IcmpOutTimeExcds
IcmpOutTimestampRep
IcmpInEchoReps
IcmpInTimeExcds
IcmpOutErrors
IcmpOutTimestamps
IcmpInEchos
IcmpInTimestamps
IcmpOutMsgs
IcmpTimestampReps
IcmpInErrors
IcmpOutAddrMaskReps IcmpOutParmProbs
IcmpInMsgs
IcmpOutAddrMasks
IcmpInParmProbs
IcmpOutDestUnreachs IcmpOutSrcQuenchs
IcmpOutRedirects
UDP MIB
UdpInDatagrams
UdpLocalAddress
UdpNoPorts
UdpInErrors
UdpLocalPort
UdpOutDatagrams
Address Translation MIB
AtIfIndex
AtPhysAddress
AtNetAddress
tcpActiveOpens
tcpConnRemPort
tcpInSegs
tcpRetransSegs
tcpAttempFails
tcpConnState
tcpMaxConn
tcpRtoAlgorithm
tcpConnLocalAddress tcpCurrEstab
tcpOutRsts
tcpRtoMax
tcpConnLocalPort
tcpEstabResets
tcpOutSegs
tcpRtoMin
tcpConnRemAddress
tcpInErrs
tcpPassiveOpens
TCP MIB
SNMP MIB
snmpEnableAuthenTraps
snmpInGetRequests
snmpInTotalSetVars
snmpInASNParseErrs
snmpInGetResponses
snmpInTraps
snmpInBadCommunityNames
snmpInNoSuchNames
snmpOutBadValues
snmpInBadCommunityUses
snmpInPkts
snmpOutGenErrs
snmpInBadValues
snmpInReadOnlys
snmpOutGetNexts
snmpInBadVersions
snmpInSetRequests
snmpOutGetRequests
snmpInGenErrs
snmpInTooBigs
snmpOutGetResponses
snmpInGetNexts
snmpInTotalReqVars
snmpOutNoSuchNames
snmpOutPkts
snmpOutTooBigs
snmpOutSetRequests
snmpOutTraps
D-2
ioLogik E2210 User’s Manual
Modbus/TCP Address Mappings
Private MIB File and SNMP Variables
Moxa also provides an SNMP to I/O MIB file that can help you monitor I/O status with SNMP
software. You can find the MIB file on the Document and Software CD.
Moxa IO MIB
DI00-Filter
DI07-Filter
DO01-Type
DO06-Type
DI00-Index
DI07-Index
DO01-Low Width
DO06-Low Width
DI00-Mode
DI07-Mode
DO01-High Width
DO06-High Width
DI00-Status
DI07-Status
DO01-PulseStart
DO06-PulseStart
DI00-Type
DI07-Type
DO02-Index
DO07-Index
DI01-Filter
DI08-Filter
DO02-Mode
DO07-Mode
DI01-Index
DI08-Index
DO02-Status
DO07-Status
DI01-Mode
DI08-Mode
DO02-Type
DO07-Type
DI01-Status
DI08-Status
DO02-Low Width
DO07-Low Width
DI01-Type
DI08-Type
DO02-High Width
DO07-High Width
DI02-Filter
DI09-Filter
DO02-PulseStart
DO07-PulseStart
DI02-Index
DI09-Index
DO03-Index
firmwareVersion
DI02-Mode
DI09-Mode
DO03-Mode
serverModel
DI02-Status
DI09-Status
DO03-Status
systemTime
DI02-Type
DI09-Type
DO03-Type
totalChannelNumber
DI03-Filter
DI10-Filter
DO03-Low Width
DI03-Index
DI10-Index
DO03-High Width
DI03-Mode
DI10-Mode
DO03-PulseStart
DI03-Status
DI10-Status
DO04-Index
DI03-Type
DI10-Type
DO04-Mode
DI04-Filter
DI11-Filter
DO04-Status
DI04-Index
DI11-Index
DO04-Type
DI04-Mode
DI11-Mode
DO04-Low Width
DI04-Status
DI11-Status
DO04-High Width
DI04-Type
DI11-Type
DO04-PulseStart
DI05-Filter
DO00-Index
DO05-Index
DI05-Index
DO00-Mode
DO05-Mode
DI05-Mode
DO00-Status
DO05-Status
DI05-Status
DO00-Type
DO05-Type
DI05-Type
DO00-Low Width
DO05-Low Width
DI06-Filter
DO00-High Width
DO05-High Width
DI06-Index
DO00-PulseStart
DO05-PulseStart
D-3
ioLogik E2210 User’s Manual
Modbus/TCP Address Mappings
Moxa IO MIB
DI06-Mode
DO01-Index
DO06-Index
DI06-Status
DO01-Mode
DO06-Mode
DI06-Type
DO01-Status
DO06-Status
D-4
E
Appendix E.
CGI Commands
Using a web browser or standard HTTP protocol will make it easier for a Security SCADA system
to monitor and control an ioLogik via CGI commands.
Syntax to get the settings is as follows. Starting with the ioLogik’s IP or URL, specify
getParam.cgi with a question mark. Then specify the command with another question mark as the
ending. The commands are case sensitive and the & sign is used to combine multiple commands.
Commands to get system information
DATE
TIME
IP
LOC
DESC
Commands to get system information
FWR_V
MOD_NAME
SN_NUM
MAC_ADDR
Commands to get DI information
DIMode_00
(0:DI, 1:COUNTER)
DIStatus_00
(0:OFF, 1:ON)
DIFilter_00
DITrigger_00
(0:LOW TO HIGH, 1:HIGH TO LOW,
2:BOTH)
DICntStart_00
(0:STOP, 1:START)
DICNT_00
DIMode_02
(0:DI, 1:COUNTER)
DIStatus_02
(0:OFF, 1:ON)
DIFilter_02
DITrigger_02
(0:LOW TO HIGH, 1:HIGH TO LOW,
2:BOTH)
DICntStart_02
(0:STOP, 1:START)
DICNT_02
Commands to get DI information
DIMode_01
(0:DI, 1:COUNTER)
DIStatus_01
(0:OFF, 1:ON)
DIFilter_01
DITrigger_01
(0:LOW TO HIGH, 1:HIGH TO LOW,
2:BOTH)
DICntStart_01
(0:STOP, 1:START)
DICNT_01
DIMode_03
(0:DI, 1:COUNTER)
DIStatus_03
(0:OFF, 1:ON)
DIFilter_03
DITrigger_03
(0:LOW TO HIGH, 1:HIGH TO LOW,
2:BOTH)
DICntStart_03
(0:STOP, 1:START)
DICNT_03
ioLogik E2210 User’s Manual
CGI Commands
DIMode_04
(0:DI, 1:COUNTER)
DIStatus_04
(0:OFF, 1:ON)
DIFilter_04
DITrigger_04
(0:LOW TO HIGH, 1:HIGH TO LOW,
2:BOTH)
DICntStart_04
(0:STOP, 1:START)
DICNT_04
DIMode_06
(0:DI, 1:COUNTER)
DIStatus_06
(0:OFF, 1:ON)
DIFilter_06
DITrigger_06
(0:LOW TO HIGH, 1:HIGH TO LOW,
2:BOTH)
DICntStart_06(0:STOP, 1:START)
DICNT_06
DIMode_08
(0:DI, 1:COUNTER)
DIStatus_08
(0:OFF, 1:ON)
DIFilter_08
DITrigger_08
(0:LOW TO HIGH, 1:HIGH TO LOW,
2:BOTH)
DICntStart_08
(0:STOP, 1:START)
DICNT_08
DIMode_10
(0:DI, 1:COUNTER)
DIStatus_10(0:OFF, 1:ON)
DIFilter_10
DITrigger_10
(0:LOW TO HIGH, 1:HIGH TO LOW,
2:BOTH)
DICntStart_10
(0:STOP, 1:START)
DICNT_10
DIMode_05
(0:DI, 1:COUNTER)
DIStatus_05
(0:OFF, 1:ON)
DIFilter_05
DITrigger_05
(0:LOW TO HIGH, 1:HIGH TO LOW,
2:BOTH)
DICntStart_05
(0:STOP, 1:START)
DICNT_05
DIMode_07
(0:DI, 1:COUNTER)
DIStatus_07
(0:OFF, 1:ON)
DIFilter_07
DITrigger_07
(0:LOW TO HIGH, 1:HIGH TO LOW,
2:BOTH)
DICntStart_07(0:STOP, 1:START)
DICNT_07
DIMode_09
(0:DI, 1:COUNTER)
DIStatus_09
(0:OFF, 1:ON)
DIFilter_09
DITrigger_09
(0:LOW TO HIGH, 1:HIGH TO LOW,
2:BOTH)
DICntStart_09
(0:STOP, 1:START)
DICNT_09
DIMode_11
(0:DI, 1:COUNTER)
DIStatus_11(0:OFF, 1:ON)
DIFilter_11
DITrigger_11
(0:LOW TO HIGH, 1:HIGH TO LOW,
2:BOTH)
DICntStart_11
(0:STOP, 1:START)
DICNT_11
Commands to get DO information
DOMode_00
(0:DO, 1:PULSE OUTPUT)
DOStatus_00
(0:OFF, 1:ON)
DOLowWidth_00
DOHighWidth_00
Commands to get DO information
DOMode_01
(0:DO, 1:PULSE OUTPUT)
DOStatus_01
(0:OFF, 1:ON)
DOLowWidth_01
DOHighWidth_01
E-2
ioLogik E2210 User’s Manual
CGI Commands
DOPulseStart_00
(0:STOP, 1:START)
DOMode_02
(0:DO, 1:PULSE OUTPUT)
DOStatus_02
(0:OFF, 1:ON)
DOLowWidth_02
DOHighWidth_02
DOPulseStart_02
(0:STOP, 1:START)
DOMode_04
(0:DO, 1:PULSE OUTPUT)
DOStatus_04
(0:OFF, 1:ON)
DOLowWidth_04
DOHighWidth_04
DOPulseStart_04
(0:STOP, 1:START)
DOMode_06
(0:DO, 1:PULSE OUTPUT)
DOStatus_06
(0:OFF, 1:ON)
DOLowWidth_06
DOHighWidth_06
DOPulseStart_06
(0:STOP, 1:START)
DOPulseStart_01
(0:STOP, 1:START)
DOMode_03
(0:DO, 1:PULSE OUTPUT)
DOStatus_03
(0:OFF, 1:ON)
DOLowWidth_03
DOHighWidth_03
DOPulseStart_03
(0:STOP, 1:START)
DOMode_05
(0:DO, 1:PULSE OUTPUT)
DOStatus_05
(0:OFF, 1:ON)
DOLowWidth_05
DOHighWidth_05
DOPulseStart_05
(0:STOP, 1:START)
DOMode_07
(0:DO, 1:PULSE OUTPUT)
DOStatus_07
(0:OFF, 1:ON)
DOLowWidth_07
DOHighWidth_07
DOPulseStart_07
(0:STOP, 1:START)
Syntax to get the settings is as follows. Starting with the ioLogik’s IP or URL, specify
setParam.cgi with a question mark. Then specify the command with another question mark as the
ending. Those commands are case sensitive and the & sign is used to combine multiple
commands.
Commands to set DI channels
DIMode_00
(0:DI, 1:COUNTER)
DIFilter_00
DITrigger_00
(0:LOW TO HIGH, 1:HIGH TO LOW,
2:BOTH)
DICntStart_00
(0:STOP, 1:START)
DIMode_02
(0:DI, 1:COUNTER)
DIFilter_02
DITrigger_02
(0:LOW TO HIGH, 1:HIGH TO LOW,
2:BOTH)
DICntStart_02
(0:STOP, 1:START)
DIMode_04
Commands to set DI channels
DIMode_01
(0:DI, 1:COUNTER)
DIFilter_01
DITrigger_01
(0:LOW TO HIGH, 1:HIGH TO LOW,
2:BOTH)
DICntStart_01
(0:STOP, 1:START)
DIMode_03
(0:DI, 1:COUNTER)
DIFilter_03
DITrigger_03
(0:LOW TO HIGH, 1:HIGH TO LOW,
2:BOTH)
DICntStart_03
(0:STOP, 1:START)
DIMode_05
E-3
ioLogik E2210 User’s Manual
CGI Commands
(0:DI, 1:COUNTER)
DIFilter_04
DITrigger_04
(0:LOW TO HIGH, 1:HIGH TO LOW,
2:BOTH)
DICntStart_04
(0:STOP, 1:START)
DIMode_06
(0:DI, 1:COUNTER)
DIFilter_06
DITrigger_06
(0:LOW TO HIGH, 1:HIGH TO LOW,
2:BOTH)
DICntStart_06
(0:STOP, 1:START)
DIMode_08
(0:DI, 1:COUNTER)
DIFilter_08
DITrigger_08
(0:LOW TO HIGH, 1:HIGH TO LOW,
2:BOTH)
DICntStart_08
(0:STOP, 1:START)
DIMode_10
(0:DI, 1:COUNTER)
DIFilter_10
DITrigger_10
(0:LOW TO HIGH, 1:HIGH TO LOW,
2:BOTH)
DICntStart_10
(0:STOP, 1:START)
(0:DI, 1:COUNTER)
DIFilter_05
DITrigger_05
(0:LOW TO HIGH, 1:HIGH TO LOW,
2:BOTH)
DICntStart_05
(0:STOP, 1:START)
DIMode_07
(0:DI, 1:COUNTER)
DIFilter_07
DITrigger_07
(0:LOW TO HIGH, 1:HIGH TO LOW,
2:BOTH)
DICntStart_07
(0:STOP, 1:START)
DIMode_09
(0:DI, 1:COUNTER)
DIFilter_09
DITrigger_09
(0:LOW TO HIGH, 1:HIGH TO LOW,
2:BOTH)
DICntStart_09
(0:STOP, 1:START)
DIMode_11
(0:DI, 1:COUNTER)
DIFilter_11
DITrigger_11
(0:LOW TO HIGH, 1:HIGH TO LOW,
2:BOTH)
DICntStart_11
(0:STOP, 1:START)
Commands to set DO channels
DOMode_00
(0:DO, 1:PULSE OUTPUT)
DOStatus_00
(0:OFF, 1:ON)
DOLowWidth_00
DOHighWidth_00
DOPulseStart_00
(0:STOP, 1:START)
DOMode_02
(0:DO, 1:PULSE OUTPUT)
DOStatus_02
(0:OFF, 1:ON)
DOLowWidth_02
DOHighWidth_02
DOPulseStart_02
(0:STOP, 1:START)
DOMode_04
Commands to set DO channels
DOMode_01
(0:DO, 1:PULSE OUTPUT)
DOStatus_01
(0:OFF, 1:ON)
DOLowWidth_01
DOHighWidth_01
DOPulseStart_01
(0:STOP, 1:START)
DOMode_03
(0:DO, 1:PULSE OUTPUT)
DOStatus_03
(0:OFF, 1:ON)
DOLowWidth_03
DOHighWidth_03
DOPulseStart_03
(0:STOP, 1:START)
DOMode_05
E-4
ioLogik E2210 User’s Manual
CGI Commands
(0:DO, 1:PULSE OUTPUT)
DOStatus_04
(0:OFF, 1:ON)
DOLowWidth_04
DOHighWidth_04
DOPulseStart_04
(0:STOP, 1:START)
DOMode_06
(0:DO, 1:PULSE OUTPUT)
DOStatus_06
(0:OFF, 1:ON)
DOLowWidth_06
DOHighWidth_06
DOPulseStart_06
(0:STOP, 1:START)
(0:DO, 1:PULSE OUTPUT)
DOStatus_05
(0:OFF, 1:ON)
DOLowWidth_05
DOHighWidth_05
DOPulseStart_05
(0:STOP, 1:START)
DOMode_07
(0:DO, 1:PULSE OUTPUT)
DOStatus_07
(0:OFF, 1:ON)
DOLowWidth_07
DOHighWidth_07
DOPulseStart_07
(0:STOP, 1:START)
E-5
F
Appendix F.
Factory Defaults
The ioLogik E2210 is configured with the following factory defaults:
Default IP address:
Default Netmask:
Default Gateway:
Communication watchdog:
Modbus/TCP Alive Check:
Modbus/TCP Timeout Interval:
192.168.127.254
255.255.255.0
0.0.0.0
Disable
On
60 sec
DI Mode:
Filter time:
Trigger for counter:
Counter status:
DI
100 × 0.5 ms
Lo to Hi
Stop
DO Mode:
DO Safe Status:
Power on status:
Low width for pulse:
DO
Off
Off
1 × 0.5 ms
Hi width for pulse:
1 × 0.5 ms
Output pulses:
0 (continuous)
Password:
Module Name:
Module Location:
SNMP:
Community:
Contact:
Location:
NONE
NONE
NONE
Enable
Public
NONE
NONE
Click&Go
NONE
G
Appendix G.
Pinouts and Cable Wiring
Ethernet Port Pinouts
Pin
Signal
1
Tx+
2
Tx-
3
Rx+
6
Rx-
1
8
Serial Port Pinouts
E2210 RS-485 Network Adapter Pin Assignment
Digital Input Wiring
Structure
ioLogik E2210 User’s Manual
Pinouts and Cable Wiring
Dry Contact
Wet Contact
Note: If you are using wet contacts, you must connect “DI COM” to power. For testing purposes,
you may connect “DI COM” to the V+ terminal of a power supply.
Example
G-2
ioLogik E2210 User’s Manual
Pinouts and Cable Wiring
Digital Output
Structure
Output Channel
* DO PWR is for powering up the field Power LED.
G-3
ioLogik E2210 User’s Manual
Pinouts and Cable Wiring
Pin Assignment of Terminal Blocks
(TB1
(TB3)
G-4
/
TB2)
H
Appendix H.
Federal Communication Commission
Interference Statement
FCC Warning!
This equipment has been tested and found to comply with the limits for a Class A digital device,
pursuant to part 15 of the FCC Rules. Operation is subject to the following two conditions: (1)
This device may not cause harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
These limits are designed to provide reasonable protection against harmful interference when the
equipment is operated in a commercial environment. This equipment generates, uses, and can
radiate radio frequency energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation of this equipment in
a residential area is likely to cause harmful interference in which case the user will be required to
correct the interference at his own expense.
I
Appendix I.
European Community (CE)
This is a Class A product. In a domestic environment, this product may cause radio interference in
which case the user may be required to take adequate measures.