Download Mitsubishi MSH-A18ND Service manual
Transcript
OB405E.qxp 09.10.14 9:16 AM Page 1 Revision E: • SPECIFICATION has been modified. Please void OB405 REVISED EDITION-D. SPLIT-TYPE AIR CONDITIONERS OUTDOOR UNIT SERVICE MANUAL No. OB405 REVISED EDITION-E Models MU-A18NDMU-A18NDMU-A24NDMU-A24NDMU-A30NDMU-A30ND- S1 S2 S1 S2 S1 S2 Indoor unit service manual MS-A• ND Series (OB404) CONTENTS MU-A18ND 1. TECHNICAL CHANGES ····································2 2. PART NAMES AND FUNCTIONS······················3 3. SPECIFICATION·················································3 4. OUTLINES AND DIMENSIONS ·························4 5. WIRING DIAGRAM ············································6 6. REFRIGERANT SYSTEM DIAGRAM ················8 7. PERFORMANCE CURVES ······························10 8. TROUBLESHOOTING······································12 9. DISASSEMBLY INSTRUCTIONS ····················21 10. PARTS LIST······················································27 11. RoHS PARTS LIST···········································30 NOTE: • This service manual describes technical data of the outdoor units. • RoHS compliant products have <G> mark on the spec name plate. For servicing of RoHS compliant products, refer to the RoHS Parts List. TM OB405E.qxp 09.10.14 9:16 AM Page 2 Revision A: • Check of solenoid valve coil has been partially modified. Revision B: • MU-A24ND - S2 has been added. Revision C: • MU-A18ND - S2 has been added. Revision D: • MU-A30ND - S2 has been added. Revision E: • SPECIFICATION has been modified. 1 TECHNICAL CHANGES w : change Frequency New Model Old Model Compressor: NH30VCD ➞ RH247NRAT Compressor: RH277NHD ➞ RH247NRAT Electricity receiving unit: Indoor unit ➞ Outdoor unit Gas pipe diameter: [15.88 ➞ [12.7 Rated voltage: 220V ➞ 220-230V 60Hz MU-A18ND - S1 MU-18TN - S1 MU-18SN w w w w w w w w Frequency 60Hz New Model MU-A24ND - S1 Old Model MU-24TN - S1 MU-24SN Outdoor unit:Unit size:W850mmoH605mmoD290mm ➞ W840mmoH850mmoD330mm w Outdoor unit:Unit size:W870mmoH850mmoD295mm ➞ W840mmoH850mmoD330mm w Compressor: NH38NBD ➞ PH33NPBT w w Electricity receiving unit: Indoor unit ➞ Outdoor unit w w Liquid refrigerant pipe diameter: [9.52 ➞ [6.35 w w Rated voltage: 220V ➞ 220-230V w w MU-A30ND - S1 New model MU-A18ND - S1 ➔ MU-A18ND - S2 • Valve cover has been added. MU-A24ND - S1 ➔ MU-A24ND - S2 • Compressor contactor has been added. MU-A30ND - S1 ➔ MU-A30ND - S2 • Solenoid valve and solenoid valve coil have been changed. 2 C1 C2 09.10.14 9:16 AM 2 Page 3 PART NAMES AND FUNCTIONS OUTDOOR UNIT MU-A18ND MU-A24ND MU-A30ND Air inlet (back and side) Air inlet Piping Drain hose Air outlet Air outlet Drain outlet 3 SPECIFICATION Outdoor model MU-A24ND MU-A18ND Function Fan motor Compressor Electrical data Capacity Capacity kW Dehumidification R/h Air flow (High/Low) K /h Power outlet A Running current (Total) A Power input (Total) W Power factor (Total) % Starting current (Total) A Compressor motor current A Fan motor current A Coefficient of performance (C.O.P) (Total) Model Output W Winding " resistance (at 20:) Model Winding " resistance (at 20:) Dimensions WOHOD mm Weight kg Sound level (High/Low) dB Fan speed (High/Low) rpm Fan speed regulator Refrigerant filling kg capacity (R22) Refrigeration oil (Model) cc MU-A30ND Cooling Single phase 220-230V, 60Hz Power supply Special remarks OB405E.qxp SSA 385 ISO 5151 4.40 5.10 1.8 2.3 2,480 15 9.94 8.52 2,100 1,800 96 96-92 40 9.02 7.60 0.55 2.10 2.83 RH247NRAT 1,200 C-R 1.43 C-S 2.06 RA6V60-MA WHT-BLK 71.2 BLK-RED 89.3 850o605o290 44 54 945 1 ISO 5151 ISO 5151 SSA 385 SSA 385 8.1 6.6 6.6 5.9 4.3 3.2 3.2 2.7 2,880 2,880/1,380 25 15( S1 ) 20( S2 ) 14.25 10.54 17.52 12.42 3,010 2,250 3,700 2,650 96-92 97-93 96 97 58 78 13.22 9.50 16.49 11.39 0.66 0.66 2.69 1.78 2.93 2.23 PH33NPBT NH44NAVT 1,500 2,000 C-R 0.84 C-R 0.62 C-S 2.09 C-S 1.40 RA6N75-BA RA6N75-AA WHT-BLK 65.0 WHT-BLK 64.2 BLK-YLW 32.9 BLK-RED 65.4 YLW-RED 32.7 840o850o330 67 76 54 55/51 790 790/490 1 2 1.40 2.20 2.40 520 (MS56) 900 (MS32N1) 1,300 (MS32N1) NOTE: Test conditions are based on ISO 5151 / SSA 385 Cooling : Indoor DB27°C WB19°C / DB29°C WB19°C Outdoor DB35°C WB24°C / DB46°C WB24°C Indoor-Outdoor piping length: 5 / 7.5 m 3 09.10.14 9:16 AM 4 Page 4 OUTLINES AND DIMENSIONS REQUIRED SPACE MU-A18ND - S1 OUTDOOR UNIT 355 350 Air in Drainage hole [16.2 20 100mm or more OB405E.qxp Unit: mm ore m 00m or m 1 100 mm or m 345 Air in 310 290 248 90 35 ore re Drainage 3holes [33 Air out 50 m 0m 50 30 or mo 35 0m m Service panel or mo re 20 50 100 157 292 3035- 605 Liquid refrigerant pipe joint Refrigerant pipe (Flared) [6.35 183 Gas refrigerant pipe joint Refrigerant pipe (flared) [12.7 161 500 850 74 MU-A18ND - S2 20 ore rm o mm 100 100 mm or m ore 345 Air in 310 290 248 90 35 Drainage hole [16.2 355 350 Air in 100mm or more REQUIRED SPACE re Drainage 3holes [33 Air out mm or mo 0 50 50 30 Service panel 20 50 100 157 292 3035- 605 Liquid refrigerant pipe joint Refrigerant pipe (Flared) [6.35 183 500 850 161 74 81 4 Gas refrigerant pipe joint Refrigerant pipe (flared) [12.7 35 0m m or mo re 09.10.14 9:16 AM Page 5 MU-A24ND MU-A30ND OUTDOOR UNIT Open as a rule 500mm or more if the front and both sides are open REQUIRED SPACE 515 299 40 100mm or more 200mm or more if there are obstacles to both sides 51 34 66 360 330 100mm or more 500 840 121 80 Open as a rule 500mm or more if the back, both sides and top are open 350mm or more 30- 850 Service panel 155 90 35- 430 OB405E.qxp 198 5 Liquid refrigerant pipe joint Refrigerant pipe (flared) [6.35(MU-A24ND) [9.52(MU-A30ND) Gas refrigerant pipe joint Refrigerant pipe (flared) [15.88 Page 6 WIRING DIAGRAM MU-A18ND OUTDOOR UNIT C2 RED WHT 4 3 2 1 2 220-230V~ ORN BLU N 220-230V~ BLU L RED ORANGE WHITE BLACK MF BRN TB1 F DSAR POWER SUPPLY 220-230V ~/N 60Hz TO INDOOR UNIT CONNECTING WHT TB2 L BLU 5 09.10.14 9:16 AM BRN OB405E.qxp C C1 BLU N RED MC S GRN/YLW BLK NAME SYMBOL NAME NAME SYMBOL SYMBOL TERMINAL BLOCK COMPRESSOR CAPACITOR FUSE (3.15A) C1 F TB1 COMPRESSOR(INNER PROTECTOR) TERMINAL BLOCK OUTDOOR FAN CAPACITOR C2 MC TB2 OUTDOOR FAN MOTOR(INNER PROTECTOR) DSAR SURGE ABSORBER MF NOTES: 1.About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing. 2.Use copper conductors only (For field wiring). 3.Symbols below indicate. : Connector : Terminal block, MU-A24ND- S1 L TB1 BRN BLU 220-230V~ RED N R BLU 4 BLK WHT 3 WHT ORN 2 RED 1 C2 N C MF ORN RED BLU F BLU GRN/YLW PE S MC BLK 2 TB2 220-230V~ C1 WHT L DSAR BRN TO INDOOR UNIT CONNECTING POWER SUPPLY ~/N 220-230V 60Hz OUTDOOR UNIT NAME SYMBOL SYMBOL NAME NAME SYMBOL TERMINAL BLOCK COMPRESSOR CAPACITOR C1 F TB1 FUSE(3.15A) TERMINAL BLOCK OUTDOOR FAN CAPACITOR C2 MC TB2 COMPRESSOR(INNER PROTECTOR) DSAR SURGE ABSORBER MF OUTDOOR FAN MOTOR(INNER PROTECTOR) NOTES: 1.Use copper conductors only (For field wiring). 2.Since the indoor and outdoor unit connecting wires have polarity, connect them according to the numbers (2,N,L). 3.Symbols below indicate. : Terminal block, : Connector 6 R 09.10.14 9:16 AM Page 7 MU-A24ND- S2 BRN TB1 1 BRN 52C C1 BLU N 4 S RED 220-230V~ BLU F GRN/YLW 2 BLU WHT ORN RED TB2 3 WHT MF 2 ORN RED C2 WHT N BLU 220-230V~ R 4 BLK 1 C MC BLK PE WHT POWER SUPPLY ~/N 220-230V 60Hz L BLU TO INDOOR UNIT CONNECTING OUTDOOR UNIT 5 BRN L 6 52C DSAR NAME SYMBOL SYMBOL NAME NAME SYMBOL TERMINAL BLOCK COMPRESSOR CAPACITOR C1 F TB1 FUSE(3.15A) TERMINAL BLOCK OUTDOOR FAN CAPACITOR C2 MC TB2 COMPRESSOR(INNER PROTECTOR) COMPRESSOR CONTACTOR DSAR SURGE ABSORBER MF 52C OUTDOOR FAN MOTOR(INNER PROTECTOR) NOTES: 1.Use copper conductors only (For field wiring). 2.Since the indoor and outdoor unit connecting wires have polarity, connect them according to the numbers (2,N,L). 3.Symbols below indicate. : Terminal block, : Connector MU-A30ND MF LEV 6 5 4 3 2 1 L CN662 YLW BLK WHT RED ORN 1 2 3 CN711 CN724 N X63 X52 SR61 X63 COM NO 12V 21S2 NR61 COM NO DEICER T61 P.C. BOARD 3TB2 1 3 5 F61 CN730 RED BLU N BRN 2 1 2 WHT C 52C C1 BLU WHT 220-230V~ 1 2 3 TAB52 X52 WHT BLU GRN/YLW PE C2 CN722 SR62 RED S MC R BLK DSAR POWER SUPPLY SYMBOL C1 C2 DSAR F61 LEV MC MF ~/N 220-230V 60Hz 6 TB1 YLW BLK WHT ORN RED RT62 RT63 OUTDOOR UNIT TO INDOOR UNIT CONNECTING OB405E.qxp WHT A1 BLU 52C A2 BLU NAME SYMBOL NAME NAME SYMBOL COMPRESSOR CAPACITOR TRANSFORMER NR61 T61 VARISTOR CONTACTOR OUTDOOR FAN CAPACITOR RT62 X52 DISCHARGE TEMPERATURE THERMISTOR SOLENOID VALVE COIL RELAY SURGE ABSORBER RT63 X63 AMBIENT TEMPERATURE THERMISTOR SOLENOID VALVE COIL FUSE(3.15A) SR61 21S2 SOLID STATE RELAY COMPRESSOR CONTACTOR EXPANSION VALVE COIL SR62 52C SOLID STATE RELAY COMPRESSOR(INNER PROTECTOR) TB1 TERMINAL BLOCK OUTDOOR FAN MOTOR(INNER PROTECTOR) TB2 TERMINAL BLOCK NOTES: 1.Use copper conductors only (For field wiring). 2.Since the indoor and outdoor unit connecting wires have polarity, connect them according to the numbers (3,N,2). 3.Symbols below indicate. : Terminal block, : Connector 7 OB405E.qxp 6 09.10.14 9:16 AM Page 8 REFRIGERANT SYSTEM DIAGRAM MU-A18ND Unit : mm OUTDOOR UNIT Refrigerant pipe {12.7 (with heat insulator) Stop Valve (with service port) Outdoor heat exchanger Compressor Strainer #100 Flared connection Capillary tube [3.0 x [1.8 x 400 Stop Valve Refrigerant pipe {6.35 (with heat insulator) MU-A24ND OUTDOOR UNIT Refrigerant pipe [15.88 (with heat insulator) Strainer #100 Stop valve (with service port) Outdoor heat exchanger Flared connection Accumulator Compressor Flared connection Stop valve Refrigerant pipe [6.35 (with heat insulator) Capillary tube [3.0 x [2.0 x 550 Refrigerant flow in cooling 8 OB405E.qxp 09.10.15 1:32 PM Page 9 MU-A30ND Unit : mm OUTDOOR UNIT Refrigerant pipe [15.88 (with heat insulator) Strainer #100 Stop valve (with service port) Outdoor heat exchanger Discharge temperature thermistor RT62 Flared connection Accumulator Compressor Capillary tube [4.0 x [2.4 x 200 Solenoid valve [4.2 x [3.0 x 50 Flared connection LEV (Expansion valve) Stop valve Refrigerant pipe [9.52 (with heat insulator) Ambient temperature thermistor RT63 Capillary tube [4.0 x [2.4 x 100 Strainer #100 Capillary tube [3.6 x [2.4 x 50 Refrigerant flow in cooling MAX.REFRIGERANT PIPING LENGTH and MAX.HEIGHT DIFFERENCE Piping size O.D : mm Refrigerant piping : m Model Max. length Max. Height A difference B Gas Liquid {12.7 MU-A18ND {6.35 MU-A24ND 30 15 {15.88 MU-A30ND {9.52 Indoor unit Max. Height difference B Max. length A Outdoor unit ADDITIONAL REFRIGERANT CHARGE(R22 : g) Refrigerant piping length (one way) Model Outdoor unit precharged MU-A18ND 1,400 MU-A24ND 2,200 MU-A30ND 2,400 7m 10m 15m 20m 30m 0 45 120 195 345 NOTE : Calculation : Xg=15g/m ✕ (Refrigerant piping length (m)-7) 9 OB405E.qxp 7 09.10.14 9:16 AM Page 10 PERFORMANCE CURVES MU-A18ND MU-A24ND MU-A30ND The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions. Since operating conditions vary according to the areas where these units are installed. The following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve. (1) GUARANTEED VOLTAGE 198 ~ 253V, 60Hz (2) AIR FLOW Air flow should be set at MAX. (3) MAIN READINGS (1) Indoor intake air wet-bulb temperature : °CWB (2) Indoor outlet air wet-bulb temperature : °CWB (3) Outdoor intake air dry-bulb temperature : °CDB (4) Total input: W Indoor air wet/dry-bulb temperature difference on the left side of the following chart shows the difference between the indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service. How to measure the indoor air wet/dry-bulb temperature difference 9.9 12.5 18.6 9.1 11.4 16.8 8.3 10.3 15.1 7.5 9.3 13.5 6.7 8.3 12.0 5.9 7.3 10.5 MS-A30ND MU-A30ND 3. 4. 5. 6. 7. MS-A24ND MU-A24ND 2. Attach at least 2 sets of wet and-dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet-and-dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high. Attach at least 2 sets of wet and dry-bulb thermometers to the outdoor air intake. Cover the thermometers to prevent direct rays of the sun. Check that the air filter is cleaned. Open windows and doors of the room. Press the EMERGENCY OPERATION switch once to start the EMERGENCY COOL MODE. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature. 10 minutes later, measure temperature again and check that the temperature does not change. MS-A18ND MU-A18ND 1. INDOOR UNIT OUTDOOR UNIT Wet and dry-bulb thermometers Wet-and dry-bulb thermometers Indoor intake air WB temperature (:) Indoor intake air WB temperature (:) Outdoor intake air DB temperature (:) Outdoor intake air DB temperature (:) 10 09.10.14 9:16 AM Page 11 OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT COOL operation ① Both indoor and outdoor units are under the same temperature/humidity condition. Dry-bulb temperature (:) Relative humidity (%) 20 50 25 60 30 70 ➁ Air flow should be set at MAX. 3 The unit of pressure has been changed to MPa on the international system of units(SI unit system). f [Gauge]) The conversion factor is : 1(MPa [Gauge]) =10.2(kgf/f 8.0 0.8 7.0 0.7 6.0 0.6 5.0 0.5 4.0 0.4 3.0 0.3 15 MU-A18ND MU-A18ND 8.0 Outdoor unit current (A) Outdoor low pressure (kgf/F [Gauge])(MPa [Gauge]) 18 20 50 30 32 70 25 (kgf/F [Gauge])(MPa [Gauge]) 7.0 6.0 5.0 4.0 15 35 (:) (%) Ambient temperature (˚C)/Ambient humidity (%) 0.8 10.0 7.0 0.7 9.0 6.0 0.6 4.0 3.0 25 60 30 32 70 35(:) (%) MU-A24ND MU-A24ND 8.0 5.0 18 20 50 Ambient temperature (˚C)/Ambient humidity (%) Outdoor unit current (A) Outdoor low pressure OB405E.qxp 0.5 0.4 8.0 7.0 6.0 0.3 5.0 15 18 20 50 25 60 30 32 70 35(:) (%) Ambient temperature (˚C)/Ambient humidity (%) 15 18 20 50 25 60 30 32 70 35(:) (%) Ambient temperature (˚C)/Ambient humidity (%) 11 OB405E.qxp 09.10.14 9:16 AM 6.0 0.6 5.0 0.5 4.0 0.4 3.0 0.3 MU-A30ND MU-A30ND 15.0 Outdoor unit current(A) Outdoor low pressure (kgf/F[Gauge])(MPa[Gauge]) Page 12 14.0 13.0 12.0 11.0 10.0 0.2 15 2.0 18 20 50 25 60 30 32 70 9.0 15 35(:) (%) Ambient temperature (˚C)/Ambient humidity (%) 8 18 20 50 25 60 30 32 70 35(:) (%) Ambient temperature (˚C)/Ambient humidity (%) TROUBLESHOOTING MU-A18ND MU-A24ND MU-A30ND 8-1. Cautions on troubleshooting 1. Before troubleshooting, check the following: 1) Check the power supply voltage. 2) Check the indoor/outdoor connecting wire for mis-wiring. 2. Take care the following during servicing. 1) Before servicing the air conditioner, be sure to turn off the main unit first with the remote controller, and then after confirming the horizontal vane is closed, turn off the breaker and / or disconnect the power plug. 2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel and the electronic control P.C. board. 3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components. 4) When connecting or disconnecting the connectors, hold the housing of Housing point Lead wiring the connector. DO NOT pull the lead wires. 3. Troubleshooting procedure 1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality. To make sure, check how many times the abnormality indication is flashing on and off before starting service work. 2) Before servicing that the connector and terminal are connected properly. 3) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the components for bursting and discolouration. 4) When troubleshooting, refer to 8-2. 12 OB405E.qxp 09.10.14 9:16 AM Page 13 8-2. Instruction of troubleshooting Start Indoor unit operates. Outdoor unit dose not operate. Outdoor unit operates in only Test Run operation. w Check room temperature thermistor. Refer to "Test point diagram and voltage". MU-A30ND Outdoor unit dose not operate even in Test Run operation. w Refer to 8-4. A "Check of outdoor unit". MS-A30ND Flash on and off at 0.5-second intervals Cause: Indoor/ Outdoor unit • Mis-wiring 2-time flash Cause: Indoor unit • Trouble of room temperature/ indoor coil thermistor Refer to 8-4. C "How to check mis-wiring (When outdoor unit dose not work)" . Check room temperature thermistor and indoor coil thermistor. Refer to "Test point diagram and voltage". w Indoor unit operates. Outdoor unit dose not operate normally. MU-A24ND - S2 MU-A30ND Outdoor unit dose not stop even if indoor unit stop. Refer to 8-4. B "Check of outdoor unit". 3-time flash Cause: Indoor unit • Trouble of indoor fan motor Refer to "Check of indoor fan motor". Indoor unit dose not receive the signal from remote controller. MU-A30ND Outdoor unit repeats start and stop. Refer to 8-4. F "Check of solenoid valve coil". 4-time flash Cause: Indoor unit • Trouble of indoor control system Indoor unit operates, when EMERGENCY OPERATION switch is pressed. Indoor unit dose not operate, when EMERGENCY OPERATION switch is pressed. Refer to "Check of remote controller and receiver P.C. board". 1. Check indoor / outdoor connecting wire. 2. Check of outdoor fuse. (MU-A18/A24ND) 3. Refer to "Check of indoor electronic control P.C. board". MU-A30ND 6-time flash Cause: Outdoor unit • Trouble of thermistor in outdoor unit Refer to 8-4. E "Check of outdoor thermistor". Replace the indoor electronic control P.C. board. OPERATION INDICATOR lamp on the indoor unit is flashing on and off. MU-A30ND 7-time flash Cause: Outdoor unit • Trouble of outdoor control system Replace the deicer P.C. board. MU-A30ND 10-time flash Cause: Outdoor unit • Trouble of low discharge temperature protection Refer to 8-4. D "Check of LEV". Refer to indoor unit service manual. "Test Run operation" means the operation within 30 minutes after EMERGENCY OPERATION switch is pressed. 13 OB405E.qxp 09.10.14 9:16 AM Page 14 8-3. Trouble criterion of main parts MU-A18ND MU-A24ND MU-A30ND Part name Discharge temperature thermistor(RT62) MU-A30ND Check method and criterion Figure Measure the resistance with a tester. Before measurement, hold the thermistor with your hands to warm it up. (Part temperature 0˚C ~ 40˚C) Refer to 8-5. "Test point diagram and voltage", "Outdoor deicer P.C. board", the chart of thermistor. Measure the resistance with a tester. (Part temperature –10˚C ~ 40˚C) Ambient temperature thermistor(RT63) MU-A30ND Refer to 8-5. "Test point diagram and voltage", "Outdoor deicer P.C. board", the chart of thermistor. Compressor (MC) Measure the resistance between the terminals with a tester. (Coil wiring temperature -10°C ~ 40°C) INNER PROTECTOR 155i 5: OPEN 90i10: CLOSE Normal Color of lead wire MU-A18ND MU-A24ND MU-A30ND C – R 1.26 " ~ 1.55 " 0.74 " ~ 0.91 " 0.54 " ~ 0.67 " C – S 1.81 " ~ 2.23 " 1.84 " ~ 2.26 " 1.23 " ~ 1.52 " WHT C P S R BLK RED Measure the resistance between the terminals with a tester. (Coil wiring temperature -10°C ~ 40°C) Outdoor fan motor (MF) INNER PROTECTOR 135i 5: OPEN 87i15: CLOSE Color of lead wire WHT – BLK BLK – RED BLK – YLW YLW – RED MU-A18ND 63 " ~ 77 " 79 " ~ 96 " – – Normal MU-A24ND 57 " ~ 70 " 58 " ~ 71 " – – MU-A30ND 57 " ~ 69 " – 29 " ~ 35 " 29 " ~ 35 " MAIN AUX. BLK RED ORN WHT MU-A18/A24ND MAIN AUX. BLK YLW RED ORN WHT MU-A30ND Solenoid valve coil (21S2) MU-A30ND Normal 37.4 " ~ 53.9 " RED1 LEV ORN4 BLU3 MU-A30ND Color of lead wire WHT – RED RED – ORN YLW – BRN BRN – BLU BRN2 LEV(Expansion valve) WHT6 YLW5 Measure the resistance with a tester. (Part temperature : 0˚C ~ 40˚C) Measure the resistance with a tester. (Part temperature : –10˚C ~ 40˚C) Normal MU-A30ND - S1 1,738 " ~ 2,125 " MU-A30ND - S2 1,230 " ~ 1,330 " P :INNER PROTECTOR 14 OB405E.qxp 09.10.14 9:16 AM Page 15 8-4. Troubleshooting flow Compressor and / or outdoor fan motor dose not operate. A Check of outdoor unit MU-A30ND Turn ON the power supply. Is there 220-230V AC to between L-N on the outdoor terminal block? No Check the outdoor power supply and connection of wiring. Yes Compressor dose not operate. Check the deicer P.C. board. Refer to 8-5. Is there 5V DC? Yes Press the EMERGENCY OPERATION switch. 3-minute time delay works. Test run operation operates for 30 minutes. Is there 220-230V AC between A1 and A2 on the compressor contactor (52C)? No Is there 220-230V AC CN730 No on the deicer P.C. board? Make the connection of wiring correct. Yes Replace the deicer P.C. board. No Replace the deicer P.C. board. No Replace the compressor contactor(52C). Yes Is there 220-230V AC between 2 on the compressor contactor(52C) and N on the outdoor terminal block? Yes Check the compressor. Outdoor fan motor dose not operate. Check the deicer P.C. board. Refer to 8-5. Is there 5V DC? Yes Press the EMERGENCY OPERATION switch. 3-minute time delay works. Test run operation operates for 30 minutes. No Is there 220-230V AC CN711 1-3 or 2-3 on the deicer P.C. board? Yes No Is there 220V AC CN730 on the deicer P.C. board? Yes Replace the deicer P.C. board. Replace the deicer P.C. board. Check the outdoor fan motor. Refer to 8-3. 15 No Make the connection of wiring correct. OB405E.qxp 09.10.14 9:16 AM Page 16 Compressor and / or outdoor fan motor dose not stop. B Check of outdoor unit MU-A24ND - S2 1 Turn OFF the power supply. 2 After 30 seconds, turn ON the power supply again. 3 Operate the unit in COOL mode by pressing the EMERGENCY OPERATION switch. 4 Operate the unit for 1 minute or more and stop it by pressing the EMERGENCY OPERATION switch again. After 30 seconds, does compressor stop ? No Yes Is there 220-230V AC between 3-N on the outdoor terminal block? No Yes Is there 220-230V AC between 1 on the compressor No contactor(52C) and N on the outdoor terminal block? Make the connection of wiring correct. Yes Replace the compressor contactor(52C). OK Is there 220-230V AC between 3-N on the indoor terminal block? Yes No Reconnect the continuity of indoor and outdoor unit connection. Replace the indoor electronic control P.C. board. After 30 seconds, does outdoor fan motor stop ? No Yes Is there 220-230V AC between 3-N on the outdoor terminal block? No Yes Is there 220-230V AC between 3 on the compressor No contactor(52C) and N on the outdoor terminal block? Make the connection of wiring correct. Yes OK Replace the compressor contactor(52C). Is there 220-230V AC between 3-N on the indoor terminal block? Yes No Reconnect the continuity of indoor and outdoor unit connection. Replace the indoor electronic control P.C. board. MU-A30ND 1 Turn OFF the power supply. 2 After 30 seconds, turn ON the power supply again. 3 Operate the unit in COOL mode by pressing the EMERGENCY OPERATION switch. 4 Operate the unit for 1 minute or more and stop it by pressing the EMERGENCY OPERATION switch again. After 30 seconds, did compressor stop? No Yes Is there 220-230V AC between A1 and A2 on the compressor contactor (52C)? Yes Ok Replace the deicer P.C. board. After 30 seconds, did outdoor fan stop? No Replace the deicer P.C. board. Yes Ok 16 No Is there 220-230V AC between 2 on the compressor contactor(52C) and N on the outdoor terminal block? Yes Replace the compressor contactor(52C). No Make the connection of wiring correct. OB405E.qxp 09.10.14 9:16 AM Page 17 When OPERATION INDICATOR lamp flashes ON and OFF in every 0.5-second. Outdoor unit dose not operate. C How to check mis-wiring w Short circuit of JPG and JPS on the indoor electronic control P.C. board enables self -check to be displayed in 3 seconds. MU-A30ND Start • Turn ON the power supply. • Press EMERGENCY OPERATION switch once. When the unit has mis-wiring, in 3 minutes, OPERATION INDICATOR lamp on indoor unit flash on and off at 0.5 second intervals. w Yes Make them sure. Is this mis-wiring, poor contact, or wire disconnection? No 1. Turn OFF the power supply and disconnect only terminal block 3 of indoor/ outdoor connecting wire on indoor side. 2. Short-circuit terminal block N-3 by lead wire. 3. Turn ON the power supply and press EMERGENCY OPERATION switch once. Is there 1V DC detected between both ends of PS132 on the indoor electronic control P.C. board ? However, the stylus of a tester would be between 0 and 20V. Yes No Replace the indoor electronic control P.C. board. • Turn OFF the power supply. • Disconnect the lead wire that terminal block N-3 is short-circuited. • Connect ON indoor/outdoor connecting wire. Turn ON the power supply. No Is there 220-230V AC between L-N on the outdoor terminal block? Check the outdoor power supply and connection of wiring. Yes No Is there 5V DC between J101 + -J401 - ? (Refer to 8-5.) Yes When EMERGENCY OPERATION is operated, is there 10V DC between both ends of R601 on the deicer P.C. board? (Refer to 8-5.) However the stylus of a tester would be between 5 ~10V. Yes No Replace the deicer P.C. board. Make the wiring between CN730 on the deicer P.C. board and outdoor terminal block correct. (Refer to 8-5.) Refer to indoor unit service manual. Replace the deicer P.C. board. 17 OB405E.qxp 09.10.14 9:16 AM Page 18 When OPERATION INDICATOR lamp flashes 10-time. Cooling mode dose not operate. D Check of LEV (Expansion valve) Remote controller model : KP0B Turn ON the power supply. 1 While pressing OPERATION SELECT button on the remote controller, press RESET button. 2 Release RESET button to confirm if all LCD in operation display section of the remote controller is displayed. 3 Release OPERATION SELECT button. MU-A30ND Remote controller model : KM04B Turn ON the power supply. 1 While pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button. 2 First, release RESET button. And release the other two buttons after all LCD in operation display section of the remote controller is displayed after 3 seconds. KP0B KM04B With remote controller set toward the indoor unit, press OPERATE/ STOP(ON/ OFF) button and confirm one beep tone. LEV operates in full-opening direction. ˚C ˚C CLOCK CLOCK AMPM AMPM AMPM Do you hear the expansion valve "click, click·······"? Do you feel the expansion valve vibrate on touching it? No Is LEV properly fixed to the expansion valve? AMPM Yes Ok No Properly fix LEV coil to the expansion valve. Yes Does the resistance of LEV have the characteristics on 8-3? Yes Replace the deicer P.C. board. NOTE : After check of LEV, do the undermentioned operation. No 1. Turn OFF the power supply and turn ON again. 2. Press the RESET button on the remote controller. Replace the LEV. When OPERATION INDICATOR lamp flashes 6-time. Thermistors in the outdoor unit are abnormal. E Check of outdoor thermistor MU-A30ND w Disconnect the connectors CN662 from the deicer P.C. board. (Check the characteristics of each thermistor.) Discharge temperature thermistor(RT62) Measure resistance between CN 662 1 and 2. Turn OFF the power supply. Ambient temperature thermistor(RT63) Replace the deicer P.C. board. Does the resistances of thermistor have the characteristics on 8-5.? No Measure resistance between CN 662 3 and 4. Replace the thermistor. Yes Connect CN662. Turn ON the power supply and press the EMERGENCY OPERATION switch. No Does the unit operate 10 minutes or more? Yes Ok W W Defective contact of the connector is considered. 18 OB405E.qxp 09.10.14 9:16 AM Page 19 F Check of solenoid valve coil MU-A30ND Outdoor unit repeats start and stop. Turn ON the power supply. Operate the unit in COOL mode by pressing the EMERGENCY OPERATION switch. After 1minute or more has passed since the compressor started, operate the solenoid valve coil by heating or cooling the ambient temperature thermistor. (Refer to Solenoid valve control.) Do you hear "click" from the solenoid valve coil? Yes No Turn ON the solenoid valve coil. (Refer to Solenoid valve control.) Ok Is there 220-230V AC CN722 on the deicer P.C. board? Yes Check of the solenoid valve coil. (Refer to 8-3.) No Replace the deicer P.C. board. Solenoid valve control The solenoid valve opens when the ambient temperature thermistor RT63 temperature reaches 49.2: or more after 1 minute has passed since the compressor turned on. Then, the solenoid valve maintains to open until the ambient temperature thermistor RT63 temperature falls 46.2: or less. Ambient temperature thermistor RT63 temperature Solenoid valve ON OFF 46.2:49.2: NOTE: The solenoid valve remains to close when the ambient temperature thermistor RT63 temperature is 49.2: or less after 1 minute has passed since the compressor turned on. 19 OB405E.qxp 09.10.14 9:16 AM Page 20 8-5. Test point diagram and voltage MU-A30ND Outdoor deicer P.C. board Ambient temperature thermistor (RT63) 100 Discharge temperature thermistor(RT62) 900 Resistance(k") 800 700 600 Resistance(k") 90 80 70 60 50 40 500 400 30 300 20 200 10 100 0 0 10 20 30 40 50 60 70 80 90 100 110 120 Temperature(:) CN662 1-2 Discharge temperature thermistor (RT62) (Refer to 8-4.E.) 0 -20 -10 0 10 20 30 40 Temperature(:) CN662 3-4 Ambient temperature thermistor (RT63) (Refer to 8-4.E.) LEV connector (CN724) Fan motor connector Varistor (CN711) (NR62) Solenoid valve coil (CN722) + } 12V DC Fuse 3.15A / 250V J101 + 5V DC J401 (Refer to 8-4. C.) } Varistor (NR61) CN7301-3 220-230-240V AC } (Refer to 8-4. A or C.) + } R601 10V DC 20 (Refer to 8-4. C.) OB405E.qxp 09.10.14 9:16 AM 9 Page 21 DISASSEMBLY INSTRUCTIONS <"Terminal with locking mechanism" Detaching points> The terminal which has the locking mechanism can be detached as shown below. There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching. (1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector has the locking mechanism. Sleeve Locking lever 1Slide the sleeve. 2Pull the terminal while pushing the locking lever. 1Hold the sleeve, and pull out the terminal slowly. Connector 9-1. MU-A18ND OUTDOOR UNIT OPERATING PROCEDURE PHOTOS 1. Removing the cabinet (1) Remove the screws of the cabinet. (2) Hold the bottom of the cabinet on both sides to remove the cabinet. (3) Remove the screws of the service panel and remove the service panel. (4) Remove the screw of the valve cover and remove the valve cover (MU-A18ND- S2 ). Photo 1 Screws of the cabinet Screws of the Service panel Screw of the valve cover Photo : MU-A18ND Photo 2 Screws of the cabinet 21 S2 OB405E.qxp 09.10.14 9:16 AM Page 22 PHOTOS OPERATING PROCEDURE 2. Removing the electrical parts Photo 3 (1) Remove the service panel and the cabinet. (2) Remove the following parts. •Compressor capacitor (C1) •Outdoor fan capacitor (C2) •Terminal blocks (TB1,TB2) Outdoor fan capacitor(C2) Compressor capacitor(C1) Photo 4 3. Removing the outdoor fan motor (1) Remove the cabinet. (Refer to 1.) (2) Disconnect the connector remove the hooked lead wire from the fan motor. (3) Remove the propeller nut and remove the propeller. (4) Remove screws fixing the fan motor. Hook Set screws of outdoor fan motor Propeller nut Propeller (5) (6) (7) (8) (9) Set screws of Outdoor fan motor Photo 5 4. Removing the compressor (1) (2) (3) (4) Terminal blocks(TB1,TB2) Remove the cabinet. (Refer to 1.) Remove the soundproof felt. Remove the terminal cover on the compressor. Disconnect lead wires from the glass terminal of the compressor. Recover gas from the refrigerant circuit. NOTE: Recover gas from the pipes until the pressure gauge shows 0 kg/cm2 (0MPa). Disconnect the welded part of the discharge pipe. Disconnect the welded part of the suction pipe. Remove nuts fixing the compressor. Remove the compressor. Discharge pipe Suction pipe Compressor Compressor nuts 22 OB405E.qxp 09.10.14 9:16 AM Page 23 9-2. MU-A24ND OUTDOOR UNIT OPERATING PROCEDURE PHOTOS 1.Removing the cabinet Photo 1 (1) Remove the screw of the service panel. (2) Remove the screws of the top panel. (3) Remove the screw of the valve cover. (4) Remove the service panel. (5) Remove the top panel. (6) Remove the valve cover. (7) Remove the screws of the front panel. (8) Remove the front panel. (9) Remove the screws of the back panel. (10) Remove the back panel. Photo 3 Screw of the top panel Screws of the cabinet Screws of the cabinet Screw of the motor support Photo 2 Screw of the service panel Screws of the top panel Screws of the back panel Screws of the front panel Screw of the valve cover Set screws of the back panel Photo 4 2. Removing the electrical parts (1) Remove the service panel and the cabinet. (2) Remove the following parts. •Compressor capacitor (C1) •Outdoor fan capacitor (C2) •Terminal blocks (TB1,TB2) •Compressor contactor (52C) (MU-A24ND- Compressor contactor (MU-A24 ND- S2 ) S2 Screws of the relay panel Terminal blocks (TB1,TB2) ) Screws of the relay panel Compressor capacitor (C1) Outdoor fan capacitor (C2) Screws of the relay panel Photo : MU-A24ND 23 S2 OB405E.qxp 09.10.14 9:16 AM Page 24 PHOTOS OPERATING PROCEDURE 3. Removing the propeller and the outdoor fan motor (1) Remove the cabinet. (Refer to 1.) (2) Remove the propeller nut and the propeller. NOTE : Loose the propeller in the rotating direction for removal. When attaching the propeller, align the mark on the propeller and the motor shaft cut section. Set the propeller in position by using the cut on the shaft and the mark on the propeller. (3) Remove the clamp of outdoor fan motor lead wire and disconnect the outdoor fan motor connector. (4) Remove the screws fixing the outdoor fan motor. (5) Remove the outdoor fan motor. Photo 5 Set screws of the outdoor fan motor Propeller nut Propeller Set screws of the outdoor fan motor Photo : MU-A24ND 4. Removing the compressor (1) (2) (3) (4) (5) (6) S2 Photo 6 Remove the cabinet. (Refer to 1.) Remove the relay panel. Remove the soundproof felt. Remove the terminal cover on the compressor. Disconnect lead wires from the compressor. Recover gas from the refrigerant circuit. Discharge pipe Terminal cover NOTE: Recover gas from the pipes until the pressure gauge shows 0 kg/cm2 (0 MPa). (7) Disconnect the welded part of the discharge pipe. (8) Disconnect the welded part of the suction pipe. (9) Remove nuts fixing the compressor. (10) Remove the compressor. Suction pipe Compressor nuts 24 OB405E.qxp 09.10.14 9:16 AM Page 25 9-3. MU-A30ND OUTDOOR UNIT OPERATING PROCEDURE PHOTOS 1.Removing the cabinet Photo 1 (1) Remove the screw of the service panel. (2) Remove the screws of the top panel. (3) Remove the screw of the valve cover. (4) Remove the service panel. (5) Remove the top panel. (6) Remove the valve cover. (7) Remove the screws of the front panel. (8) Remove the front panel. (9) Remove the screws of the back panel. (10) Remove the back panel. Screw of the top panel Screws of the cabinet Screws of the cabinet Photo 3 Photo 2 Screw of the motor support Screw of the service panel Screws of the top panel Screws of the back panel Screws of the front panel Screw of the valve cover Set screws of the back panel 2. Removing the deicer P.C. board Photo 4 (1) Remove the service panel and the cabinet. (2) Disconnect all the connectors and the terminals on the deicer P.C. board. (3) Remove the deicer P.C. board. Screws of the relay panel Deicer P.C. board Terminal blocks (TB1,TB2) Screws of the relay panel Compressor Compressor Outdoor fan contactor capacitor(C1) capacitor (C2) (52C) 25 OB405E.qxp 09.10.14 9:16 AM Page 26 PHOTOS OPERATING PROCEDURE 3. Removing the propeller and the outdoor fan motor (1) Remove the cabinet. (Refer to 1.) (2) Remove the propeller nut and the propeller. NOTE : Loose the propeller in the rotating direction for removal. When attaching the propeller, align the mark on the propeller and the motor shaft cut section. Set the propeller in position by using the cut on the shaft and the mark on the propeller. (3) Remove the clamp of outdoor fan motor lead wire and disconnect the outdoor fan motor connector. (4) Remove the screws fixing the outdoor fan motor. (5) Remove the outdoor fan motor. Photo 5 Set screws of the outdoor fan motor Propeller nut Propeller Set screws of the outdoor fan motor Compressor 4. Removing the compressor (1) (2) (3) (4) (5) (6) Photo 6 Remove the cabinet. (Refer to 1.) Remove the relay panel. Remove the soundproof felt. Remove the terminal cover on the compressor. Disconnect lead wires from the compressor. Recover gas from the refrigerant circuit. NOTE: Discharge pipe Recover gas from the pipes until the pressure gauge shows 0 kg/cm2 (0 MPa). (7) Disconnect the welded part of the discharge pipe. (8) Disconnect the welded part of the suction pipe. (9) Remove nuts fixing the compressor. (10) Remove the compressor. Suction pipe Terminal cover Compressor nuts 26 OB405E.qxp 09.10.14 9:16 AM 10 Page 27 PARTS LIST (non-RoHS compliant) MU-A18ND 10-1. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS 19 20 18 1 17 16 15 14 2 13 12 3 11 10 4 5 6 7 8 9 Part numbers that are circled are not shown in the illustration. No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Part No. E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E07 817 A27 817 817 141 496 075 949 817 A27 140 139 819 817 818 561 A27 890 795 798 895 816 817 627 A49 001 233 233 232 521 501 515 506 900 290 290 661 662 650 245 301 630 630 383 374 374 351 353 009 936 382 241 Part Name BACK PANEL BACK PANEL CABINET GRILLE PROPELLER MOTOR SUPPORT COMPRESSOR RUBBER SET COMPRESSOR BASE BASE STOP VALVE(GAS) STOP VALVE(LIQUID) VALVE COVER SERVICE PANEL OUTDOOR FAN MOTOR OUTDOOR HEAT EXCHANGER OUTDOOR HEAT EXCHANGER SURGE ABSORBER TERMINAL BLOCK TERMINAL BLOCK OUTDOOR FAN CAPACITOR COMPRESSOR CAPACITOR HANDLE CAPILLARY TUBE FUSE FUSE HOLDER Q'ty/unit Symbol in Wiring MU-A18ND - S1 MU-A18ND Diagram 1 1 1 1 1 1 1 1 1 1 3 3 1 1 MC 1 1 1 1 1 1 1 1 1 1 1 MF 1 1 1 1 DSAR 1 1 TB2 1 1 TB1 1 1 C2 1 1 C1 1 1 1 1 1 1 F 1 1 27 S2 Remarks 3RUBBERS/SET RH247NRAT {12.7 { 6.35 RA6V60 - 3P 3P 3.0+/440V AC 35+/440V AC {3.0o{1.8o400 3.15A OB405E.qxp 09.10.14 9:16 AM Page 28 PARTS LIST (non-RoHS compliant) MU-A24ND MU-A30ND 10-2. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS 27 26 25 24 22 23 A 21 B 1 20 19 2 18 3 17 4 16 5 7 17 15 8 6 14 9 10 28 11 12 13 OB405E.qxp 09.10.14 9:16 AM Page 29 PARTS LIST (non-RoHS compliant) MU-A24ND MU-A30ND 10-2. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS Part numbers that are circled are not shown in the illustration. No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 Part No. E02 E02 E02 E02 E02 E02 E07 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E02 E07 819 890 947 950 951 214 070 889 890 819 819 819 527 784 951 889 947 890 889 819 819 819 890 795 889 817 890 951 A19 951 889 816 819 817 726 890 819 A49 336 948 948 262 527 625 947 947 001 297 630 630 301 301 501 508 290 290 232 009 521 506 900 900 661 662 662 932 650 245 309 383 374 374 374 351 451 340 340 353 353 233 009 515 640 493 382 385 936 937 936 936 936 490 492 241 Part Name TOP PANEL OUTDOOR HEAT EXCHANGER OUTDOOR HEAT EXCHANGER OUTDOOR FAN MOTOR OUTDOOR FAN MOTOR PROPELLER PROPELLER NUT BASE BASE CABINET HANDLE FAN GUARD COMPRESSOR RUBBER SET COMPRESSOR COMPRESSOR STOP VALVE(GAS) STOP VALVE(LIQUID) STOP VALVE(LIQUID) ACCUMULATOR VALVE COVER SERVICE PANEL THERMISTOR SURGE ABSORBER TERMINAL BLOCK TERMINAL BLOCK TERMINAL BLOCK OUTDOOR FAN CAPACITOR DEICER P.C. BOARD COMPRESSOR CONTACTOR COMPRESSOR CONTACTOR COMPRESSOR CAPACITOR COMPRESSOR CAPACITOR BACK PANEL(OUT) HANDLE MOTOR SUPPORT EXPANSION VALVE EXPANSION VALVE COIL FUSE VARISTOR CAPILLARY TUBE(TAPER PIPE) CAPILLARY TUBE(TAPER PIPE) CAPILLARY TUBE CAPILLARY TUBE CAPILLARY TUBE SOLENOID VALVE COIL SOLENOID VALE FUSE HOLDER Symbol in Wiring MUDiagram A24ND - MF MF MC MC RT62, RT63 DSAR TB2 TB2 TB1 C2 52C 52C C1 C1 LEV F,F61 NR61 Q'ty/unit S1 MUA24ND - 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 4 1 1 1 1 4 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 MUA30ND - 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 4 1 1 1 1 1 1 1 1 1 1 1 1 4RUBBERS/SET PH33NPBT NH44NAVT {15.88 {6.35 {9.52 DISCHARGE, AMBIENT 3P 3P 3P 4.0+/440V AC FIGUREB FIGUREA 55+/440V AC 35+/440V AC 1 1 1 1 1 1 1 1 1 1 1 3.15A 1 1 RA6N75RA6N75- 1 1 1 1 1 Remarks S1 1 1 1 21S2 29 S2 {4.2x{3.0x50 {3.6x{2.4x50 {4.0x{2.4x200 {4.0x{2.4x100 {3.0x{2.0x550 OB405E.qxp 11 09.10.14 9:16 AM Page 30 RoHS PARTS LIST (RoHS compliant) MU-A18ND 11-1. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS 19 20 18 1 17 16 15 14 2 13 12 3 11 10 4 5 30 6 7 8 9 09.10.14 9:16 AM Page 31 RoHS PARTS LIST (RoHS compliant) MU-A18ND 11-1. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS Part numbers that are circled are not shown in the illustration. No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 RoHS OB405E.qxp G G G G G G G G G G G G G G G G G G G G G G G G G G Part No. E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E17 817 A27 817 817 141 496 075 949 817 A27 140 139 819 817 818 561 A27 890 795 798 895 816 817 627 A49 001 233 233 232 521 501 515 506 900 290 290 661 662 650 245 301 630 630 383 374 374 351 353 009 936 382 241 Part Name BACK PANEL BACK PANEL CABINET GRILLE PROPELLER MOTOR SUPPORT COMPRESSOR RUBBER SET COMPRESSOR BASE BASE STOP VALVE(GAS) STOP VALVE(LIQUID) VALVE COVER SERVICE PANEL OUTDOOR FAN MOTOR OUTDOOR HEAT EXCHANGER OUTDOOR HEAT EXCHANGER SURGE ABSORBER TERMINAL BLOCK TERMINAL BLOCK OUTDOOR FAN CAPACITOR COMPRESSOR CAPACITOR HANDLE CAPILLARY TUBE FUSE FUSE HOLDER Q'ty/unit Symbol in Wiring MU-A18ND - S1 MU-A18ND Diagram 1 1 1 1 1 1 1 1 1 1 3 3 1 1 MC 1 1 1 1 1 1 1 1 1 1 1 MF 1 1 1 1 DSAR 1 1 TB2 1 1 TB1 1 1 C2 1 1 C1 1 1 1 1 1 1 F 1 1 31 S2 Remarks 3RUBBERS/SET RH247NRAT {12.7 { 6.35 RA6V60 - 3P 3P 3.0+/440V AC 35+/440V AC {3.0o{1.8o400 3.15A OB405E.qxp 09.10.14 9:16 AM Page 32 RoHS PARTS LIST (RoHS compliant) MU-A24ND MU-A30ND 11-2. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS 27 26 25 24 22 23 A 21 B 1 20 19 2 18 3 17 4 16 5 7 17 15 8 6 14 9 10 32 11 12 13 09.10.14 9:16 AM Page 33 RoHS PARTS LIST (RoHS compliant) MU-A24ND MU-A30ND 11-2. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS Part numbers that are circled are not shown in the illustration. No. RoHS OB405E.qxp 1 G G 2 G G 3 G 4 G 5 G G 6 G 7 G 8 G 9 G 10 G G 11 G 12 G G 13 G 14 G 15 G 16 G 17 G 18 G G 19 G 20 G 21 G G 22 G G 23 G G 24 G 25 G 26 G 27 G 28 G 29 G 30 G 31 G G 32 G G G 33 G G G 34 G G 35 G 36 G Part No. E12 E12 E12 E12 E12 E12 E17 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E12 E17 819 890 947 950 951 214 070 889 890 819 819 819 527 784 951 889 947 890 889 819 819 819 890 795 889 817 890 951 B19 A19 951 889 816 819 817 726 890 819 A49 336 948 B18 948 262 527 625 947 B19 947 B18 001 297 630 630 301 301 501 508 290 290 232 009 521 506 900 900 661 662 662 932 650 245 309 383 374 374 374 351 451 451 340 340 353 353 233 009 515 640 493 382 385 936 936 937 936 936 936 490 490 492 492 241 Part Name TOP PANEL OUTDOOR HEAT EXCHANGER OUTDOOR HEAT EXCHANGER OUTDOOR FAN MOTOR OUTDOOR FAN MOTOR PROPELLER PROPELLER NUT BASE BASE CABINET HANDLE FAN GUARD COMPRESSOR RUBBER SET COMPRESSOR COMPRESSOR STOP VALVE (GAS) STOP VALVE (LIQUID) STOP VALVE (LIQUID) ACCUMULATOR VALVE COVER SERVICE PANEL THERMISTOR SURGE ABSORBER TERMINAL BLOCK TERMINAL BLOCK TERMINAL BLOCK OUTDOOR FAN CAPACITOR DEICER P.C. BOARD DEICER P.C. BOARD COMPRESSOR CONTACTOR COMPRESSOR CONTACTOR COMPRESSOR CAPACITOR COMPRESSOR CAPACITOR BACK PANEL (OUT) HANDLE MOTOR SUPPORT EXPANSION VALVE EXPANSION VALVE COIL FUSE VARISTOR CAPILLARY TUBE (TAPER PIPE) CAPILLARY TUBE (TAPER PIPE) CAPILLARY TUBE (TAPER PIPE) CAPILLARY TUBE CAPILLARY TUBE CAPILLARY TUBE SOLENOID VALVE COIL SOLENOID VALVE COIL SOLENOID VALE SOLENOID VALE FUSE HOLDER Q'ty/unit Symbol MUMUMUMUin Wiring Diagram A24ND - A24ND - A30ND - A30ND - MF MF MC MC RT62, RT63 DSAR TB2 TB2 TB1 C2 S1 S2 S1 S2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 4 1 1 1 1 4 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 4 1 1 1 1 4 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Remarks RA6N75RA6N75- 4RUBBERS/SET PH33NPBT NH44NAVT {15.88 {6.35 {9.52 DISCHARGE, AMBIENT 3P 3P 3P 4.0+/440V AC 1 52C 52C C1 C1 LEV F,F61 NR61 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 21S2 21S2 1 1 1 1 1 33 1 FIGUREB FIGUREA 55+/440V AC 35+/440V AC 3.15A {4.2x{3.0x50 {4.2x{3.0x50 {3.6x{2.4x50 {4.0x{2.4x200 {4.0x{2.4x100 {3.0x{2.0x550 OB405E.qxp 09.10.14 9:16 AM Page 34 34 OB405E.qxp 09.10.14 9:16 AM Page 35 35 OB405E.qxp 09.10.14 9:16 AM Page 36 TM HEAD OFFICE: TOKYO BLDG, 2-7-3, MARUNOUCHI, CHIYODAKU, TOKYO 100-8310, JAPAN C Copyright 2005 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD Distributed in Oct. 2009. No.OB405 REVISED EDITION-E 5 Distributed in May 2006. No.OB405 REVISED EDITION-D 106 Distributed in Nov. 2005. No.OB405 REVISED EDITION-C 106 Distributed in Jun. 2005. No.OB405 REVISED EDITION-B 106 Distributed in May 2005. No.OB405 REVISED EDITION-A 106 Reprinted in Apr. 2005. No.OB405 100 Distributed in Mar. 2005. No.OB405 6 Made in Japan New publication, effective Oct. 2009 Specifications subject to change without notice.